8 Technical Data
8.1 Features
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
129
8 Technical Data
The following tables show the performance characteristics for the various
DE1 variable speed starter models together with the motor power that are
compatible with them.
8.1 Features
→
The motor power allocation is based on the rated operational
current.
→
The motor power is the mechanical power at the shaft of a
normal, four pole, internally or externally ventilated alternating
current asynchronous motor with 1.500 rpm at 50 Hz or
1.800 rpm at 60 Hz.
Part no.
Rated operational current
Frame size
Degree of protection
Assigned motor power
I
e
FS
IP
P (230 V, 50 Hz)
P (220 - 240 V, 60 Hz)
[A]
[kW]
[A]
1)
[HP]
[A]
1)
Mains supply voltage: 1 AC 230 V, 50/60 Hz, Output voltage: 3 AC 230 V, 50/60 Hz
DE1-121D4…
1.4
FS1
IP20
0.25
1.4
1/3
1.4
DE1-122D3…
2.3
FS1
IP20
0.37
2
1/2
2.2
DE1-122D7…
2.7
FS1
IP20
0.55
2.7
1/2
2.2
DE1-124D3…
4.3
FS1
IP20
0.75
3.2
1
4.2
DE1-127D0…
7
FS1
IP20
1.5
6.3
2
6.8
DE1-129D6…
9.6
FS2
IP20
2.2
8.7
3
9.6
1) The rated motor currents apply to normal internally and surface-cooled three-phase motors
Part no.
Rated operational current
Frame size
Degree of protection
Assigned motor power
I
e
FS
IP
P (400 V, 50 Hz)
P (440 - 480 V, 60 Hz)
[A]
[kW]
[A]
1)
[HP]
[A]
1)
Mains supply voltage: 3 AC 400 V, 50 Hz / 480 V, 60 Hz,
Output voltage: 3 AC 400 V, 50 Hz / 440 - 480 V, 60 Hz
DE1-341D3…
1.3
FS1
IP20
0.37
1.1
1/2
1.1
DE1-342D1…
2.1
FS1
IP20
0.75
1.9
1
2.1
DE1-343D6…
3.6
FS1
IP20
1.5
3.6
2
3.4
DE1-345D0…
5
FS2
IP20
2.2
5
3
4.8
DE1-346D6…
6.6
FS2
IP20
3
6.6
3
4.8
DE1-348D5…
8.5
FS2
IP20
4
8.5
5
7.6
DE1-34011…
11.3
FS2
IP20
5.5
11.3
7.5
11
DE1-34016…
16
FS2
IP20
7.5
15.2
10
14
1) The rated motor currents apply to normal internally and surface-cooled three-phase motors
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...