1 DE1 series
1.6 Voltage categories
16
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
1.6 Voltage categories
DE1 variable speed starters are subdivided into two voltage categories:
•
DE1-
12
…
•
Single-phase mains connection 230 V
•
U
LN
= 1~, 200 - 240 V
±
10 %, 50/60 Hz
•
I
e
: 1.4 - 9.6 A
•
Motor: 0.25 - 2.2 kW (230 V), 1/3 - 3 hp (230 V)
figure 9:
DE1-12…FN-N20N (with radio interference suppression filter)
figure 10: DE1-12…NN-N20N (without radio interference suppression filter)
•
DE1-
34
…
•
three-phase mains connection 400 V
•
U
LN
= 3~, 380 - 480 V
±
10 %, 50/60 Hz
•
I
e
: 1.3 - 16 A
•
Motor: 0.37 - 7.5 kW (400 V), 1/2 - 10 HP, (460 V)
figure 11: DE1-34…FN-N20N (with radio interference suppression filter)
figure 12: DE1-34…NN-N20N (without radio interference suppression filter)
Mains, U
LN
= 1 ~ 200 - 240 V ±10 %
L1
N
PE
L1/L
L2/N
U
V
W
I
e
230 V
Motor
M
3 ∼
EMC Filter (DE1-12…FN-…)
Mains, U
LN
= 1 ~ 200 - 240 V ±10 %
L1
N
PE
L1/L
L2/N
U
V
W
I
e
230 V
Motor
M
3 ∼
Mains, U
LN
= 3 ~ 380 - 480 V ±10 %
400 V
440 - 480 V
L1
L2
L3
L1/L
L2/N
L3
U
V
W
I
e
Motor
M
3 ∼
PE
EMC Filter (DE1-34…FN-…)
Mains, U
LN
= 3 ~ 380 - 480 V ±10 %
400 V
440 - 480 V
L1
L2
L3
L1/L
L2/N
L3
U
V
W
I
e
Motor
M
3 ∼
PE
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...