3 Installation
3.3 Electrical Installation
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
47
figure 36: PE connection for the individual variable speed starters (example)
Three-phase
commoning link
Can be used with the following maximum number of device sizes
DILM12-XDSB0/3
3 x FS1
2 x FS1 + 1 x FS2
2 x FS2
DILM12-XDSB0/4
4 x FS1
3 x FS1 + 1 x FS2
1 x FS1 + 2 x FS2
1)
DILM12-XDSB0/5
5 x FS1
4 x FS1 + 1 x FS2
2 x FS1 + 2 x FS2
1)
3x FS2
1)
1) These combinations may result in the total of the individual input currents (DE1-34…) exceeding the
three-phase commoning link's and incoming connection block's ampacity (35 A).
WARNING
Each individual DE1-34… variable speed starter must be
connected to the mains voltage protective earth conductor.
L1/L L2/N L3
L1/L L2/N L3
L1/L L2/N L3