11 List of parameters
176
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
P-40
168
RUN
rw
Action@Communication Loss
0 - 4
0
SWD, communication loss
Used to define how the DE1 variable speed starter
will behave if it loses communication with
SmartWire-DT:
0
: No response (continued operation)
1
: Alarm message (continued operation)
2
: STOP function with deceleration time P-04 if
P-05 = 1 (ramp)
3
: Shutdown (uncontrolled deceleration, free run-
down)
4
: Shutdown with fault message
Note:
P-36 can be used to set a delay for the response
to a loss of communication.
–
P-41
169
RUN
rw
ParameterAccess
0/1
0
Parameter Access
0
: All parameters can be changed from any source
(SmartWire-DT, drivesConnect, external keypad).
1
: All parameters are locked and can only be
changed via SmartWire-DT or Modbus.
PNU
M
odbus ID
Access right
Name
Value
DS
Description
pa
ge
RUN,
STOP
ro
/rw
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...