11 List of parameters
178
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
P00-14
ro
Actual Switching
Frequency
16 kHz
Switching frequency, active
Instantaneous value of switching frequency. If P-32 = 0
(temperature management enabled for heat sink), this
value may be lower than the value set in P-29.
P00-15
ro
DC-Link0 Log
( - DC-Link7 Log)
000
DC link voltage before fault
Shows the last eight DC link voltage values (V) before the
device was switched off due to a fault.
Scan time: 256 ms
(use the arrow keys to scroll through the values)
1
: DC-Link0
…
8
: DC-Link7
P00-16
ro
Heatsink0 Log
( - Heatsink7 Log)
00
Heat sink temperature before fault
Shows the last eight heat sink temperature values (°C)
before the device was switched off due to a fault.
Scan time: 30 s
(use the arrow keys to scroll through the values)
1
: Heat sink temperature 0
…
8
: Heat sink temperature 7
P00-17
ro
MotorCurrent0 Log
(- MotorCurrent7 Log)
0.0
Motor current before fault
Shows the last eight motor current values (A) before the
device was switched off due to a fault.
Scan time: 256 ms
(use the arrow keys to scroll through the values)
1
: Motor current 0
…
8
: Motor current 7
P00-18
ro
Application version
0.00
(00C0)
DE1 version
Software version and checksum, displayed separately (use
the arrow keys to switch between the two)
P00-19
ro
Serial number
123456
(78-000)
Serial number
Serial number from left to right, split into two sections (use
the arrow keys to switch between the two sections)
P00-20
ro
DriveInformation
0.37 - 7.50
DE1 information
Rating in kW
PNU
Modbus ID
Access
right
Name
Value
Description
ro/rw
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...