9 Accessory devices
9.11 Sine filter DX-SIN3…
162
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
Table 49: Assigned sine filters
Device Type
Rated current
Sine filter
I
e
Part no.
I
e
u
k
1)
A
A
%
DE1-121D4…
1.4
DX-SIN3-004
4
7.5
DE1-122D3…
2.3
DX-SIN3-004
4
7.5
DE1-122D7…
2.7
DX-SIN3-004
4
7.5
DE1-124D3…
4.3
DX-SIN3-010
10
7
DE1-127D0…
7
DX-SIN3-010
10
7
DE1-129D6…
9.6
DX-SIN3-010
10
7
DE1-341D3…
1.3
DX-SIN3-004
4
7.5
DE1-342D1…
2.1
DX-SIN3-004
4
7.5
DE1-343D6…
3.6
DX-SIN3-004
4
7.5
DE1-345D0…
5
DX-SIN3-010
10
7
DE1-346D6…
6.6
DX-SIN3-010
10
7
DE1-348D5…
8.5
DX-SIN3-010
10
7
DE1-34011…
11
DX-SIN3-016
16
7.5
DE1-34016…
16
DX-SIN3-016
16
7.5
1) Typical voltage drop at the sine filter relative to output voltage U
2
Notes:
Sine filters DX-SIN3… should only be operated with fixed pulse frequencies (P-32 = 1):
• Permissible fixed pulse frequency (f
PWM
) of DE1 device: 8 - 16 kHz (= P-29)
• Maximum sine filter power supply (U
max
): 520 V ±0%
• Maximum 120 s with 150% I
e
or 30 s with 200% I
e
• Maximum permissible output frequency f
2
: 150 Hz
• Maximum permissible ambient air temperature: 40 °C
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...