6 Parameters
6.5 Parameter description
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
103
6.5.6.3 Smartwire DT
When the device is used together with SmartWire-DT, the control terminals
can be configured as shown below by using parameter P-15.
P-12 = 9 (SWD c SWD reference)
P-12 = 11 (Local control, SWD reference),
enable signal with DI1,
external fault message at DI3.
Table 28: Configuration with SmartWire-DT and P-12 (= 9, 11)
→
Process data access via SmartWire-DT (P-12 = 9, 10, 11, 12, 13)
requires a SmartWire-DT DX-NET-SWD3 module.
→
For more information and technical data on SmartWire-DT and
the DX-NET-SWD3 interface module, please refer to manual
MN04012009Z.
P-15
(Mode)
DI1
DI2
DI3
AI1/DI4
0
ENA
n. F.
n. F.
n. F.
1
ENA
n. F.
EXTFLT
n. F.
2
ENA
n. F.
n. F.
n. F.
3
ENA
n. F.
EXTFLT
n. F.
4
ENA
n. F.
n. F.
n. F.
5
ENA
n. F.
EXTFLT
n. F.
6
ENA
n. F.
n. F.
n. F.
7
ENA
n. F.
EXTFLT
n. F.
8
ENA
n. F.
n. F.
n. F.
9
ENA
n. F.
EXTFLT
n. F.
n. F. = no Function.
When configured this way, the control terminals “n.F.” will have no
function whatsoever!
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...