9 Accessory devices
9.10 Motor Choke DX-LM3…
160
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
Table 48: Motor chokes that should be used
Device Type
Motor choke that should be used
Voltage class
Part no.
Rated operational
current
I
e
230 V
400 V/480 V
A
DE1-121D4…
DE1-341D3…
DX-LM3-005
5
DE1-122D3…
DE1-342D1…
DX-LM3-005
5
DE1-122D7…
DE1-343D6…
DX-LM3-005
5
DE1-124D3…
DE1-345D0…
DX-LM3-005
5
DE1-127D0…
DE1-346D6…
DX-LM3-008
8
DE1-129D6…
DE1-348D5…
DX-LM3-011
11
–
DE1-34011…
DX-LM3-011
11
–
DE1-34016…
DX-LM3-016
16
Notes:
• Maximum motor choke power supply (U
max
): 750 V ±0%
• Maximum permissible output frequency f
2
: 200 Hz
• Maximum permissible pulse frequency (f
PWM
) for DE1 device: 24 kHz (= P-29)