10 Fault messages
10.3 Fault list
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
167
6 x
05
PS-trF
Power section fault
• Fault message from the power section's output.
→
Check the connection to the motor (short-circuit, earth
fault).
→
Disconnect the cable from terminals U, V, W.
→
If the fault message cannot be reset, please contact
your closest Eaton office.
7 x
0C
SC-trF
Communication fault
→
Check the connection between the RJ45 interface and
external devices.
→
Make sure that every device on the network has a
unique address.
8 x
0A
P-dEf
Default parameter settings
• The parameter's default setting has been loaded.
→
Press the STOP button on the external keypad.
9 x
–
FLt-dc
DC residual ripple
• The DC link voltage's residual ripple is too high.
→
Check whether all three mains voltage phases are
present and whether the voltage difference between the
mains phases is smaller than 3%.
→
Reduce the motor load.
→
If the fault message cannot be reset, please contact
your closest Eaton office.
10 x
12
4-20F
Live zero error
• The current signal at analog input AI1 has fallen below
3 mA.
→
Check the current source and the wiring to control
terminals 4 and 0 V.
11 x
09
V-t
Under-temperature
• The ambient temperature is lower than -10
°
C (frost).
→
Raise the ambient temperature to a temperature above
-10
°
C.
12 x
10
th-FLt
Thermistor fault
• Faulty thermistor on internal heat sink.
→
Please contact your closest Eaton representative.
13 x
11
dAtA-F
Data error
• The modified parameters were not saved (flash memory) and
the default settings have been loaded instead.
→
If the problem occurs again, please contact your closest
Eaton representative.
1) 2 Hz "Fault Code" LED flashing frequency with 2-second pause
2) Optional external keypad
Fault Code
LED
(2 Hz + 2s)
1)
Modbus
RTU
[hex]
Display
DX-KEY-LED)
2)
Designation
Possible cause/fixes
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...