11 List of parameters
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
171
P-11
139
RUN
rw
V-Boost
0.0 - 40.0 %
0.0 %
Voltage Boost
Output voltage boost at low output frequencies.
The value set here will be the start voltage and
will be calculated as a percentage of the motor's
rated operating voltage (P-07). V-Boost is
effective up to approx. 50% of the motor's rated
frequency (P09).
Note:
The voltage increase function will result in a
higher starting torque and will improve torque
behaviour at low speeds. In addition, the motor
current will be increased, resulting in increased
motor heating.
P-12
140
RUN
rw
ProcessDataAccess
0 - 13
0
Process data access (control level)
Used to select the control and signal paths that
will be used.
Regardless of the control level selected, the
enable signal at DI1 (FWD) or DI2 (REV) will
always take priority.
0
: Control terminals (see P-15)
1
: Keypad (external option), clockwise rotating
field (FWD) by pressing the START button
2
: Keypad (external option). Depending on
whether there is an enable signal at DI1 (FWD) or
DI2 (REV), pressing the START button will enable
a clockwise rotating field (FWD) or a
counterclockwise rotating field (REV). Pressing
the START button again will reverse the operating
direction.
Note:
The operating direction that is active before the
STOP command will be stored.
3
: Modbus RTU
4 - 8
: no function (reserve)
9
: SWD (SmartWire-DT)
10
: SmartWire-DT control, with frequency
reference value set using control terminal 4 (AI1,
0 V)
11
: SmartWire-DT for frequency reference value
and control via control terminals 1 to 4 (DI1 - DI4)
12
: SmartWire-DT with automatic switch to
control terminals in case of communication loss
13
: SmartWire-DT and digital setpoint value (UP,
DOWN) via control terminals (see P-15)
98ff
P-13
1)
141
STOP
ro
Last fault
Most recent fault
– eighth most
recent fault
-
Fault log history
Display memory containing the eight most recent
fault messages
P-14
142
RUN
rw
Password
0 - 65535
0
Access code
Password protection for the extended parameter
set (P-15 through P-41). The password can be set
using parameter P-38.
Default settings: 101
PNU
M
odbus ID
Access right
Name
Value
DS
Description
pa
ge
RUN,
STOP
ro
/rw
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...