11 List of parameters
174
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
P-29
1)
157
STOP
rw
Switching frequency
4 - 32 kHz
10 - 20 kHz
16 kHz
Switching frequency
Switching frequency (audible pulse frequency) of
IGBTs in power section
DE1-12… : 4/8/12/16/24/32 kHz
DE1-34… : 10/12/14/16/18/20 kHz
P-30
158
STOP
rw
Start mode
EdgE-r,
Auto-0 -
Auto-9
Auto-0
Start mode
EdgE-r:
Following power ON or reset, the drive
will not start if a start signasl (FWD/REV) is still
present. To start DE1 a rising edge is necessary.
Auto-0
: The device will restart automatically
after a fault message if the supply voltage is not
switched off and the start command (FWD or REV)
is still present.
Auto-1
-
Auto-9
: 1 to 9 automatic start attempts
at 20-s intervals if the supply voltage is not
switched off and the start command (FWD or REV)
is still present. If the DE1 device does not start
automatically after the last selected start
attempt, it will be switched off with the fault
message. It will then have to be RESET (supply
voltage OFF-ON (power cycling), start command
with rising edge, or STOP command).
–
P-31
159
RUN
rw
OvervoltageControl
0/1
0
Overvoltage control
The overvoltage control function (OV) will prevent
the DE1 device from being switched off if too
much energy is being fed into the DC link during
the motor's regenerative operation and the DC
link voltage increases to an excessive value as a
result:
0
: OV active. During deceleration, the configured
ramp time (P-02) will be automatically
lengthened. During continuous operation, the
output frequency (speed) will be temporarily
increased.
1
: OV locked (shutdown with a fault message).
P-32
160
STOP
rw
AutoThermalManagement
0/1
0
Switching frequency, temperature
management
The temperature management function will
automatically lower the switching frequency
(P-29) if the heat sink in the power section gets
too hot.
This will reduce switching losses and prevent a
shutdown due to excess temperature.
0
: activated
1
: deactivated
Note:
This function must be turned off (1 = constant
switching frequency) if the DE1 device is being run
with a sine filter at its output.
PNU
M
odbus ID
Access right
Name
Value
DS
Description
pa
ge
RUN,
STOP
ro
/rw
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...