7 Modbus RTU
7.4 Operating mode Modbus RTU
DE1 variable speed starter
09/14 MN040011EN
www.eaton.com
123
7.4.3.2 Output process data
The output process data is used to monitor the DE1 variable speed starter.
Table 39: Output process data
Status and fault word (ID 6)
Information regarding the device status and fault messages is specified in
the status and fault word.
ID
Description
Scaling Factor
Unit/Format
6
Status and fault word
–
Binary code
7
Actual value (speed, frequency)
0.1
Hz
8
Motor current
0.1
A
9
reserved
–
–
10
reserved
–
–
11
DI status
–
Binary code
12
type
–
WORD
13
Power
1
kW/HP
14
Voltage level
1
V
15
Software version, control section
–
WORD
16
Software version, power section
–
WORD
17
DE1 identification
–
WORD
18
reserved
–
–
19
reserved
–
–
20
Value AI1
0.1
%
21
Value AI2
0.1
%
22
Reference input speed
1
RPM
23
DC link voltage
1
V
24
Temperature in power section
1
°C
25
DE1 operating time
1
h
26
DE1 operating time
1
min/s
27
DE1 operating time since the last fault message
1
h
28
DE1 operating time since the last fault
1
min/s
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
Fault word
Statusword
Содержание PowerXL DE1 series
Страница 4: ...II ...
Страница 36: ...2 Engineering 2 5 Motor Selection 32 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 68: ...3 Installation 3 6 Block diagrams 64 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 132: ...7 Modbus RTU 7 4 Operating mode Modbus RTU 128 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 146: ...8 Technical Data 8 4 Dimensions 142 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 172: ...10 Fault messages 10 3 Fault list 168 DE1 variable speed starter 09 14 MN040011EN www eaton com ...
Страница 186: ...182 DE1 variable speed starter 09 14 MN040011EN www eaton com ...