COMMUNICATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
93
X-Slot Cards
X-Slot cards allow the UPS to communicate in a variety of networking
environments and with different types of devices. The BladeUPS has
two available communication bays for any X-Slot card, including:
S
ConnectUPS-X Web/SNMP Card
- has SNMP and HTTP capabilities as
well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It has a built-in
switching hub that allows three additional network devices to be
connected to the network without the requirement of additional
network drops. In addition, a Powerware Environmental Monitoring
Probe can be attached to obtain humidity, temperature, smoke alarm,
and security information.
S
Relay Interface Card
- has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On
bypass.
S
Modbus
®
Card
- allows you to continuously and reliably monitor the
UPSs in your Building Management System (BMS).
S
Industrial Relay Card (IRC)
- is used to indicate the operating status of
the UPS system using the customer's monitoring equipment. The
IRC uses four isolated normally-open or normally-closed dry relay
contacts to indicate the UPS status. Normal, Bypass, Battery, and
Alarm mode can be monitored.
S
Modem Card
- provides out-of-band remote notification and monitoring
using modem communication directly to cell phones and pagers.
See Figure 47 on page 89 for the location of the two X-Slot
communication bays.
Relay Interface Card
Modbus Card
Modem Card
ConnectUPS-X Web/SNMP Card
Industrial Relay Card
Figure 50. Optional X-Slot Cards
Содержание Powerware BladeUPS
Страница 1: ...Powerware BladeUPS 12 kVA User s Guide ...
Страница 8: ...TABLE OF CONTENTS EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com iv ...
Страница 108: ...COMMUNICATION EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 100 ...
Страница 132: ...TROUBLESHOOTING EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 124 ...
Страница 136: ...WARRANTY EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 128 ...
Страница 137: ......
Страница 138: ... 1642016493 164201649 3 ...