OPERATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
79
9.
Verify that the “Batteries Disconnected” alarm has cleared. Verify
that no other alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
10.
Press any button on the front panel display to activate the menu
options. Select TURN UPS ON/OFF, TURN UPS ON, and press the
button.
11.
Confirm the selection. Press and hold the
button for three
seconds, until the UPS stops beeping.
Verify that the
indicator illuminates solid, indicating that the
UPS is operating normally and any loads not connected through the
Load Connector are now energized.
If the
indicator is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
The UPS should be in Normal mode. By default, Normal mode
operates on the High Efficiency setting (see “Normal Mode” on
page 76).
12.
To energize a load connected through the Load Connector, switch
the load connector circuit breaker to the ON (
|
) position.
13.
Press the
ESC
button until the Eaton Powerware logo appears.
Содержание Powerware BladeUPS
Страница 1: ...Powerware BladeUPS 12 kVA User s Guide ...
Страница 8: ...TABLE OF CONTENTS EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com iv ...
Страница 108: ...COMMUNICATION EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 100 ...
Страница 132: ...TROUBLESHOOTING EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 124 ...
Страница 136: ...WARRANTY EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 128 ...
Страница 137: ......
Страница 138: ... 1642016493 164201649 3 ...