Programmable Signal Inputs
The UPS incorporates two programmable signal inputs (see Figure 47 on
page 89). Use of non-polar (relay) control input is recommended. The
pins must be shorted with maximum resistance of 10 ohm in order to
activate the specific input.
NOTE
See Figure 51 on page 94 for the polarity and verify these connections if polarity
control is required.
Table 7 shows the programmable settings for the signal inputs.
Table 7. Programmable Signal Inputs
Signal
Description
on generator
If active, the High Efficiency setting is disabled (BladeUPS 12i
model only) and battery tests are disabled.
charger off
If active, the battery charge function is disabled. In a utility
power outage, the discharge of batteries is supported.
on/OFF
If active, the UPS output turns off regardless of the mode of
operation. Auxiliary power, communication, and
rectifier/battery charger remain functional. Restart is initiated
immediately when this signal is inactive.
force bypass
If active, the UPS is forced to static bypass operation
regardless of the bypass status.
ext battery breaker
If active, the UPS knows that the external batteries are
disconnected.
empty
Not in use (default).
Use the programmable signal inputs to emulate some of the features
usually seen on larger three-phase systems. For example:
S
Configure the signal from a smoke detector or water leak detector to
shut down the system.
S
Configure a vibration sensor or air conditioner sensor to shut down
the system.
S
Set actions for alarms from a generator, such as disabling the charger
for an undersized generator or shutdown for a failed generator.
S
Configure an ATS (automatic transfer switch) sensor to transfer the
system to Bypass mode.
Содержание Powerware BladeUPS
Страница 1: ...Powerware BladeUPS 12 kVA User s Guide ...
Страница 8: ...TABLE OF CONTENTS EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com iv ...
Страница 108: ...COMMUNICATION EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 100 ...
Страница 132: ...TROUBLESHOOTING EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 124 ...
Страница 136: ...WARRANTY EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 128 ...
Страница 137: ......
Страница 138: ... 1642016493 164201649 3 ...