UPS MAINTENANCE
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
111
5.
Insert the replacement module by sliding it carefully into the
cabinet. Verify that it seats firmly against the rear of the cabinet.
Reinstall the electronics module locking screw.
6.
Parallel configurations only.
Reconnect the redundant signal cable(s).
7.
Replace the UPS front cover (see Figure 57):
Plug the LCD cable from the control panel on the front cover into
the connector on the electronics module. Use care to gently loop
the LCD cable in front of the electronics module.
Push the top of the front cover firmly into place, and then push the
bottom firmly into place.
8.
Verify that there are no alarms indicated on the control panel.
9.
Transfer the UPS to Normal mode.
LCD Cable
Figure 57. Replacing the UPS Front Cover