UPS Startup and Shutdown
To start up or shut down a UPS, see:
S
“Starting a Standalone UPS” on page 78
S
“Starting a Parallel System” on page 80
S
“Starting the UPS on Internal Bypass” on page 81
S
“Standalone UPS Shutdown” on page 83
S
“Individual Paralleled UPS Shutdown” on page 84
S
“Parallel System Shutdown” on page 85
Starting a Standalone UPS
To start a standalone UPS (see Figure 32 on page 49):
1.
Verify that all UPS circuit breakers are in the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power.
2.
Verify that the UPS power cord is plugged in.
3.
Switch on utility power where the UPS is connected.
4.
Switch the UPS input circuit breaker to the ON (
|
) position.
5.
Wait for the UPS front panel display to illuminate.
The
indicator flashes on the UPS.
6.
Check the UPS front panel display for active alarms or notices
(other than “Batteries Disconnected”). Resolve any active alarms
before continuing. See “Troubleshooting” on page 119.
7.
Switch the UPS battery circuit breaker to the ON (
|
) position.
8.
If optional EBMs are installed, switch all EBM battery circuit
breakers to the ON (
|
) position.
Содержание Powerware BladeUPS
Страница 1: ...Powerware BladeUPS 12 kVA User s Guide ...
Страница 8: ...TABLE OF CONTENTS EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com iv ...
Страница 108: ...COMMUNICATION EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 100 ...
Страница 132: ...TROUBLESHOOTING EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 124 ...
Страница 136: ...WARRANTY EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 128 ...
Страница 137: ......
Страница 138: ... 1642016493 164201649 3 ...