OPERATION
EATON
Powerware
®
BladeUPS
®
(12 kVA) User's Guide
S
164201649 Rev 3
www.powerware.com
83
Standalone UPS Shutdown
To shut down a standalone UPS (see Figure 32 on page 49):
1.
Switch the load connector circuit breaker to the OFF (O) position.
NOTE
The load connector breaker controls the load connector only, not the output power.
2.
Press any button on the front panel display to activate the menu
options. Select TURN UPS ON/OFF, TURN UPS OFF, and press the
button.
3.
Confirm the selection. Press and hold the
button for three
seconds, until the UPS stops beeping.
The output relays open, the UPS transfers to Standby mode, and
the
indicator turns off.
4.
Switch the UPS battery circuit breaker to the OFF (O) position.
5.
If optional EBMs are installed, switch all EBM battery circuit
breakers to the OFF (O) position.
6.
Switch the UPS input circuit breaker to the OFF (O) position.
7.
Press the
ESC
button until the Eaton Powerware logo appears.
8.
Switch off utility power where the UPS is connected.
Содержание Powerware BladeUPS
Страница 1: ...Powerware BladeUPS 12 kVA User s Guide ...
Страница 8: ...TABLE OF CONTENTS EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com iv ...
Страница 108: ...COMMUNICATION EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 100 ...
Страница 132: ...TROUBLESHOOTING EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 124 ...
Страница 136: ...WARRANTY EATON Powerware BladeUPS 12 kVA User s Guide S 164201649 Rev 3 www powerware com 128 ...
Страница 137: ......
Страница 138: ... 1642016493 164201649 3 ...