To minimize disturbance to the wires through casual contact,
secure
the
DC
cable to the rack frame using multiple cable
ties. Use at least four cable ties, a minimum of
4
inches
(10.16 cm.) apart. The Þrst tie should be within
6 inches
(15.24 cm.)
of the terminal block. (A cable tie mount is
provided.)
9
Turn on the
DC
power source
.
The
LEDs
on the front panel ßash as the
DL600E
unit
automatically runs the
Self Test
at power up. The
PWR/TEST
LED
blinks yellow and then
turns green when the test is
successful. If the test fails, the
LED
turns red for ten seconds
and then green.