background image

 

 

 

These state-of-the-art panel meters are designed for 
accurate measurement of the AC RMS voltage, AC 
RMS current, frequency, active power and power 
factor in single-phase systems. The current 
transformer ratio can be set between 5/5A and 
5000/5A via front panel buttons. 

Devices have separate inputs for supply and 
measurement. 

The unit allows both manual selection of the display 
channel and automatic scrolling. 

Changing Display Selection: 

By using the 

MENU

       button, voltage, current, 

active power, power factor and frequency can be 
selected and read from display. Every depression on 
the 

MENU      

 button will display the next 

measurement. 

60 seconds after the last keypress, the display will 
return automatically to the default display mode. 
However the defult display mode is selectable by 
programming. 

 

Any measured parameter can be set as the default 
display. Automatic  parameter scrolling is also 
provided. Selections are stored into a non-volatile 
memory and is not affected from power failures. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

Press 

MENU

 button  

for 3 sec. 
 

 

 

 

Press 

Up

 or 

Down

  

buttons until  
requested Current 
Transformer Ratio is 
displayed. 

 

 

 

Press 

MENU 

button  

for saving current 
transformer ratio and 
displaying default selection. 

 

 

 

Press 

Up

 or 

Down

  

buttons until  
requested display mode 
appears.

 

– Auto scroll values every 5 

sec. 
1 =voltage     4= power factor 
2= current      5= frequency 
3= active power 

 

 

 

Press 

MENU 

button for 

saving default selection and 
exit for settings. 

 

 

 

 

 Do not open the unit. There is no serviceable parts 

inside. 

 Fuses must be connected to the power supply and 

phase voltage inputs, in close proximity of the unit. 

 Fuses must be of fast type (FF) with a maximum 

rating of 6A. 

 Disconnect all power before working on equipment. 

 When the unit is connected to the network do not 

touch terminals. 

 Short circuit terminals of unused current 

transformers. 

 Do not try to clean the device with solvent or the 

like. Only clean with a dry cloth. 

 Verify correct terminal connections before applying 

power. 

 Electrical equipment should be serviced only by 

competent service personnel. No responsibility is 
assured by the manufacturer or any of its 
subsidiaries for any consequences arising out of 
the use of this material. 

 Only for front panel flush mounting.

 

 

Before installation 

 Read the user manual carefully, determine the 

correct connection diagram. 

 Remove all connectors and mounting brackets 

from the unit, then pass the unit through the 
mounting opening. 

 Put mounting brackets and tighten. Do not tighten 

too much, this can brake the enclosure. 

 Make electrical connections with connectors 

removed from sockets, then place connectors to 
their sockets.

 

 Note that the power supply terminal is separated 

from measurement terminals, with common neutral 
point.

 

 

 

 

 

 

 

 

 

Failure to follow below 
instructions will result in 
death or serious injury

 

 

PRECAUTIONS FOR INSTALLATION 

AND SAFE USE

 

SETTING THE CURRENT 

TRANSFROMER RATIO 

AND THE DEFAULT DISPLAY

 

INTRODUCTION

 

DM-0101 DIGITAL MULTIMETER 

72x72 & 96x48mm SIZES

 

DA-0101 DIGITAL AMMETER 

96x96mm SIZES

 

 

MENU  

 



MENU  

 

MENU  

 

Отзывы: