5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in
parameter
group 5-1* Digital Inputs
except for option
[32] Pulse input
.
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in
parameter
group 5-1* Digital Inputs
except for option
[32] Pulse input
.
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
*
No operation This parameter is active when VLT
®
General
Purpose I/O MCB 101 is installed in the
frequency converter. The parameter contains
all options and functions listed in
parameter
group 5-1* Digital Inputs
except for option
[32] Pulse input
.
5-19 Terminal 37 Safe Stop
Use this parameter to configure the Safe Torque Off functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a fieldbus, Digital I/O, or by pressing [RESET]
on the LCP). When the VLT
®
PTC Thermistor Card MCB 112 is
mounted, configure the PTC options to get the full benefit from
the alarm handling.
Option:
Function:
[1]
*
Safe Stop Alarm Coasts the frequency converter when
Safe Torque Off is activated. Manual
reset from LCP, digital input, or
fieldbus.
[3]
Safe Stop
Warning
Coasts the frequency converter when
Safe Torque Off is activated (terminal
37 off). When the Safe Torque Off
circuit is re-established, the frequency
converter continues without manual
reset.
[4]
PTC 1 Alarm
Coasts the frequency converter when
Safe Torque Off is activated. Manual
reset from LCP, digital input, or
fieldbus.
[5]
PTC 1 Warning
Coasts the frequency converter when
Safe Torque Off is activated (terminal
37 off). When the Safe Torque Off
circuit is re-established, the frequency
5-19 Terminal 37 Safe Stop
Use this parameter to configure the Safe Torque Off functionality.
A warning message makes the frequency converter coast the
motor and enables the automatic restart. An alarm message
makes the frequency converter coast the motor and requires a
manual restart (via a fieldbus, Digital I/O, or by pressing [RESET]
on the LCP). When the VLT
®
PTC Thermistor Card MCB 112 is
mounted, configure the PTC options to get the full benefit from
the alarm handling.
Option:
Function:
converter continues without manual
reset, unless a digital input set to
[80]
PTC Card 1
is still enabled.
[6]
PTC 1 & Relay A This option is used when the VLT
®
PTC Thermistor Card MCB 112 gates
with a stop key through a safety relay
to terminal 37. Coasts the frequency
converter when Safe Torque Off is
activated. Manual reset from LCP,
digital input, or fieldbus.
[7]
PTC 1 & Relay
W
This option is used when the VLT
®
PTC Thermistor Card MCB 112 gates
with a stop key through a safety relay
to terminal 37. Coasts the frequency
converter when Safe Torque Off is
activated (terminal 37 off). When the
Safe Torque Off circuit is re-
established, the frequency converter
continues without manual reset,
unless a digital input set to
[80] PTC
Card 1
is still enabled.
[8]
PTC 1 & Relay
A/W
This option makes it possible to use a
combination of alarm and warning.
[9]
PTC 1 & Relay
W/A
This option makes it possible to use a
combination of alarm and warning.
Parameter Description
VLT
®
AQUA Drive FC 202
80
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02