3.9.2 8-1* Ctrl. Word Settings
8-10 Control Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are visible in the LPC display.
For guidelines in selection of
[0] Frequency converter profile
and
[1] PROFIdrive profile
, refer to the
design guide
of the related
product. For more guidelines in the selection of
[1] PROFIdrive
profile
,
[5] ODVA
, and
[7] CANopen DSP 402
, see the
installation
guide
for the installed fieldbus.
Option:
Function:
[0]
*
FC profile
[1]
PROFIdrive profile
[5]
ODVA
Available only with VLT
®
DeviceNet MCA 104 and
VLT
®
EtherNet/IP MCA
121.
[7]
CANopen DSP 402
8-13 Configurable Status Word STW
This parameter enables configuration of bits 12–15 in the status
word.
Array [16]
Option:
Function:
[0]
No function
[1]
*
Profile Default
The function corresponds to the profile
default selected in
.
[2]
Alarm 68 Only
Only set if
alarm 68, Safe Torque Off
occurs.
[3]
Trip excl Alarm
68
Set if a trip occurs, unless
alarm 68, Safe
Torque Off
is set to execute the trip.
[10]
T18 DI status
The bit indicates the status of terminal
18.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[11]
T19 DI status
The bit indicates the status of terminal
19.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[12]
T27 DI status
The bit indicates the status of terminal
27.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[13]
T29 DI status
The bit indicates the status of terminal
29.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[14]
T32 DI status
The bit indicates the status of terminal
32.
0 indicates that the terminal is low.
8-13 Configurable Status Word STW
This parameter enables configuration of bits 12–15 in the status
word.
Array [16]
Option:
Function:
1 indicates that the terminal is high.
[15]
T33 DI status
The bit indicates the status of terminal
33.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[16]
T37 DI status
The bit indicates the status of terminal
37.
0 indicates that T37 is low (Safe Torque
Off).
1 indicates that T37 is high (normal).
[20]
CTW Timeout
Toggle Inverse
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, frequency converter, brake
resistor, or thermistor.
[30]
Brake fault
(IGBT)
Output is logic 1 when the brake IGBT is
short-circuited. Use this function to
protect the frequency converter if there
is a fault on the brake modules. Use the
output/relay to cut out the main voltage
from the frequency converter.
[40]
Out of ref range
[60]
Comparator 0
See
parameter group 13-1* Comparators
. If
comparator 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See
parameter group 13-1* Comparators
. If
comparator 1 is evaluated as true, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See
parameter group 13-1* Comparators
. If
comparator 2 is evaluated as true, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See
parameter group 13-1* Comparators
. If
comparator 3 is evaluated as true, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See
parameter group 13-1* Comparators
. If
comparator 4 is evaluated as true, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See
parameter group 13-1* Comparators
. If
comparator 5 is evaluated as true, the
output goes high. Otherwise, it is low.
[70]
Logic Rule 0
See
parameter group 13-4* Logic Rules
. If
logic rule 0 is evaluated as true, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See
parameter group 13-4* Logic Rules
. If
logic rule 1 is evaluated as true, the
output goes high. Otherwise, it is low.
Parameter Description
VLT
®
AQUA Drive FC 202
102
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3