23-61 Continuous Bin Data
Range:
Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press [OK] and
step between elements with [
▲
] and [
▼
].
10 counters with the frequency of
occurrence for the operating variable
monitored, sorted according to the following
intervals:
•
Counter [0]: 0–<10%.
•
Counter [1]: 10–<20%.
•
Counter [2]. 20–<30%.
•
Counter [3]: 30–<40%.
•
Counter [4]: 40–<50%.
•
Counter [5]: 50–<60%.
•
Counter [6]. 60–<70%.
•
Counter [7]: 70–<80%.
•
Counter [8]. 80–<90%.
•
Counter [9]: 90–<100% or
maximum.
The above minimum limits for the intervals
are the default limits. These can be changed
in
parameter 23-65 Minimum Bin Value
Starts to count when the frequency
converter is powered up for the first time. All
counters can be reset to 0 in
parameter 23-66 Reset Continuous Bin Data
.
23-62 Timed Bin Data
Array [10]
Range:
Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press [OK] and
step between elements with [
▲
] and [
▼
].
10 counters with the frequency of occurrence
for the operating data monitored sorted
according to the intervals as for
parameter 23-61 Continuous Bin Data
.
Starts to count at the date/time programmed
in
parameter 23-63 Timed Period Start
, and
stops at the time/date programmed in
parameter 23-64 Timed Period Stop
. All
counters can be reset to 0 in
parameter 23-67 Reset Timed Bin Data
.
23-63 Timed Period Start
Array [10]
Range:
Function:
Size
related
*
[ 0 -
0 ]
NOTICE
The frequency converter has no back-up
of the clock function. The set date/time
is reset to default (2000-01-01 00:00)
after a power-down unless a real-time
clock-module with back-up is installed.
Therefore, the logging is stopped until
date/time is readjusted in
parameter 0-70 Date and Time
. In
, it is possible
to program a warning if the clock has
not been set properly, for example after
a power-down.
NOTICE
When mounting VLT
®
Analog I/O option
MCB 109, a battery back-up of the date
and time is included.
Set the date and time at which the trending
starts the update of the timed bin counters.
Date format depends on setting in
parameter 0-71 Date Format
, and time format
on setting in
.
23-64 Timed Period Stop
Range:
Function:
Size
related
*
[ 0 -
0 ]
NOTICE
When mounting VLT
®
Analog I/O
Option MCB 109, a battery back-up of
the date and time is included.
Set the date and time at which the trend
analyses must stop updating the timed bin
counters.
Date format depends on the setting in
parameter 0-71 Date Format
, and time format
on the setting in
.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
199
3
3