3.3.10 1-6* Load Depend. Setting
1-60 Low Speed Load Compensation
Range:
Function:
100
%
*
[0 -
300 %]
NOTICE
Parameter 1-60 Low Speed Load Compen-
sation
has no effect when
parameter 1-10 Motor Construction
=
[1]
PM, non-salient SPM
.
Enter the % value to compensate voltage in
relation to load when the motor is running at
low speed and obtain the optimum U/f charac-
teristic. The motor size determines the frequency
range within which this parameter is active.
Motor size [kW]
Changeover [Hz]
0.25–7.5
<10
11–45
<5
55–550
<3–4
Table 3.8 Changeover Frequency
130BA046.11
60%
0%
100%
U
m
Changeover
f
out
Par.1-60
Par.1-61
Illustration 3.10 Low Speed Load Compensation
1-61 High Speed Load Compensation
Range:
Function:
100
%
*
[0 -
300 %]
NOTICE
Parameter 1-61 High Speed Load Compen-
sation
has no effect when
parameter 1-10 Motor Construction
=
[1]
PM, non-salient SPM
.
Enter the % value to compensate voltage in
relation to load when the motor is running at
high speed and obtain the optimum U/f charac-
teristic. The motor size determines the frequency
range within which this parameter is active.
1-61 High Speed Load Compensation
Range:
Function:
Motor size [kW]
Changeover [Hz]
0.25–7.5
>10
11–45
<5
55–550
<3–4
Table 3.9 Changeover Frequency
1-62 Slip Compensation
Range:
Function:
0 %
*
[-500 -
500 %]
NOTICE
Parameter 1-62 Slip Compensation
has no
effect when
=
[1] PM, non-salient SPM
.
To compensate for tolerances in the value of
n
M,N
, enter the % value for slip compensation.
Slip compensation is calculated automatically,
that is based on the nominal motor speed n
M,N
.
1-63 Slip Compensation Time Constant
Range:
Function:
Size
related
*
[0.05 -
5 s]
NOTICE
Parameter 1-63 Slip Compensation
Time Constant
has no effect when
parameter 1-10 Motor Construction
=
[1] PM, non-salient SPM
.
Enter the slip compensation reaction
speed. A high value results in slow
reaction, and a low value results in quick
reaction. If low-frequency resonance
problems occur, use a longer time setting.
1-64 Resonance Damping
Range:
Function:
Size
related
*
[0 -
500 %
]
NOTICE
Parameter 1-64 Resonance Damping
has
no effect when
=
[1] PM, non-salient SPM
.
Enter the resonance damping value. Set
parameter 1-64 Resonance Damping
and
parameter 1-65 Resonance Damping Time
Constant
to help eliminate high frequency
resonance problems. To reduce resonance
oscillation, increase the value of
parameter 1-64 Resonance Damping
.
Parameter Description
Programming Guide
MG20OB02