4-16 Torque Limit Motor Mode
Range:
Function:
Size
related
*
[ 0 -
1000.0 %
]
Enter the maximum torque limit for motor
operation. The torque limit is active in the
speed range up to and including the
nominal motor speed set in
parameter 1-25 Motor Nominal Speed
. To
protect the motor from reaching the
stalling torque, the default setting is 1.1 x
the rated motor torque (calculated value).
See also
for further details.
If a setting in
to
is changed,
is not automatically reset
to the default setting.
4-17 Torque Limit Generator Mode
Range:
Function:
100
%
*
[ 0 -
1000.0 %
]
Enter the maximum torque limit for generator-
mode operation. The torque limit is active in
the speed range up to and including the
nominal motor speed (
). Refer to
for further details.
If a setting in
to
parameter 1-28 Motor Rotation Check
is
changed,
parameter 4-17 Torque Limit Generator
is not automatically reset to the default
settings.
4-18 Current Limit
Range:
Function:
160.0
%
*
[1.0 -
1000.0 %
]
Enter the current limit for motor and
generator operation. To protect the motor
from reaching the stalling torque, the default
setting is 1.1 x the rated motor torque
(calculated value). If a setting in
parameter 1-00 Configuration Mode
to
parameter 1-26 Motor Cont. Rated Torque
is
changed,
parameter 4-18 Current Limit
is not
automatically reset to the default setting.
4-19 Max Output Frequency
Range:
Function:
Size
related
*
[ 1 -
590
Hz]
NOTICE
This parameter cannot be adjusted
while the motor is running.
NOTICE
When
parameter 1-10 Motor Construction
is set to
[1] PM, non-salient SPM
, the
maximum value is limited to 300 Hz.
4-19 Max Output Frequency
Range:
Function:
Enter the maximum output frequency value.
Parameter 4-19 Max Output Frequency
specifies
the absolute limit on the frequency converter
output frequency for improved safety in
applications where unintended overspeeding
must be avoided. This absolute limit applies to
all configurations and is independent of the
setting in
parameter 1-00 Configuration Mode
3.6.2 4-5* Adj. Warnings
Define adjustable warning limits for current, speed,
reference, and feedback.
NOTICE
Not visible in the display, only in MCT 10 Set-up
Software.
4-50 Warning Current Low
Range:
Function:
0
A
*
[ 0 -
par.
4-51
A]
Warnings are shown on the display, programmed
output, or fieldbus.
130BA064.10
(P 4-18)
(P 4-51)
(P 4-50)
(P 4-11)
(P 4-53)
(P 4-52)
(P 4-13)
I
HIGH
I
LOW
n
LOW
n
HIGH
n
motor
I
motor
REF
ON REF
IN RANGE
I
LIM
n
MAX
n
MIN
[RPM]
Illustration 3.27 Low Current Limit
Enter the I
LOW
value. When the motor current drops
below this limit (I
LOW
), the display reads
Current low
.
The signal outputs can be programmed to produce
a status signal on terminal 27 or 29, and on relay
output 01 or 02. Refer to
4-51 Warning Current High
Range:
Function:
Size
related
*
[ par.
4-50 - par.
16-37 A]
Enter the I
HIGH
value. When the motor
current exceeds this limit (I
HIGH
), the
display reads
Current high
. The signal
outputs can be programmed to produce
a status signal on terminal 27 or 29, and
on relay output 01 or 02. Refer to
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
73