3.22.1 25-0* System Settings
Parameters related to control principles and configuration
of the system.
25-00 Cascade Controller
Option:
Function:
For operation of multiple devices (pump/fan)
systems where capacity is adapted to actual
load with speed control combined with on/off
control of the devices. For simplicity, only
pump systems are described.
To enable the cascade controller functionality,
set
parameter 1-00 Configuration Mode
to
option
[3] Closed Loop
.
[0] Disabled
The cascade controller is not active. All built-in
relays assigned to pump motors in the cascade
function are de-energized. If a variable speed
pump is connected to the frequency converter
directly (not controlled by a built-in relay), this
pump/fan is controlled as a single-pump
system.
[1] Basic
Cascade Ctrl
The cascade controller is active and stages/
destages pump according to load on the
system.
[2] Motor
Alternation
Only
25-02 Motor Start
Option:
Function:
Motors are connected to mains directly with a
contactor or with a soft starter. When the value of
is set to an option
other than
[0] Direct on Line
, then
parameter 25-50 Lead Pump Alternation
is automat-
ically set to the default of
[0] Direct on Line
.
[0]
*
Direct
on Line
Each fixed speed pump is connected to mains
directly via a contactor.
[1]
Soft
Starter
Each fixed speed pump is connected to mains via
a soft starter.
[2]
Star
Delta
Fixed pumps connected with star-delta starters
are staged in the same way as pumps connected
with soft starters. They are destaged in the same
way as pumps connected directly to mains.
25-04 Pump Cycling
Option:
Function:
To provide equal hours of operation with fixed
speed pumps, the pump used can be cycled. The
selection of pump cycling is either
first in – last out
or equal running hours for each pump.
25-04 Pump Cycling
Option:
Function:
[0] Disabled The fixed speed pumps are connected in the order
1–2 and disconnected in the order 2–1 (first in–last
out).
[1] Enabled The fixed speed pumps are connected/discon-
nected to have equal running hours for each
pump.
25-05 Fixed Lead Pump
Option: Function:
Fixed lead pump is a configuration when the variable
speed pump is connected directly to the frequency
converter. If a contactor is applied between frequency
converter and pump, this contactor is not controlled by
the frequency converter.
If operating with
parameter 25-50 Lead Pump Alternation
set to other than
[0] Off
, set this parameter to
[0] No
.
[0] No The lead pump function can alternate between the
pumps controlled by the 2 built-in relays. Connect 1
pump to the built-in relay 1, and the other pump to
relay 2. The pump function (cascade pump1 and
cascade pump2) is automatically assigned to the relays
(maximum 2 pumps can in this case be controlled by
the frequency converter).
[1] Yes The lead pump is fixed (no alternation) and connected
directly to the frequency converter.
Parameter 25-50 Lead Pump Alternation
is automatically
set to
[0] Off
. Built-in relays, relay 1 and relay 2, can be
assigned to separate fixed speed pumps. In total, the
frequency converter can control 3 pumps.
25-06 Number of Pumps
Range:
Function:
2
*
[ 2 -
9 ]
The number of pumps connected to the cascade
controller including the variable speed pump. If the
variable speed pump is connected directly to the
frequency converter, and the other fixed speed
pumps (lag pumps) are controlled by the 2 built-in
relays, 3 pumps can be controlled. If both the
variable speed and fixed speed pumps are to be
controlled by built-in relays, only 2 pumps can be
connected.
If
parameter 25-05 Fixed Lead Pump
is set to
[0] No
: 1
variable speed pump and 1 fixed speed pump, both
controlled by built-in relay. If
is set to
[1] Yes
: 1 variable speed pump
and 1 fixed speed pump controlled by built-in
relays.
1 lead pump, see
parameter 25-05 Fixed Lead Pump
2 fixed speed pumps controlled by built-in relays.
Parameter Description
VLT
®
AQUA Drive FC 202
208
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3