26-00 Terminal X42/1 Mode
Option:
Function:
Terminal X42/1 can be programmed as an
analog input accepting a voltage or input
from either Pt1000 (1000
Ω
at 0
°
C (32
°
F)) or
Ni 1000 (1000
Ω
at 0
°
C (32
°
F)) temperature
sensors. Select the mode.
[2] Pt 1000 [
°
C]
and
[4] Ni 1000 [
°
C]
if
operating in Celsius, or
[3] Pt 1000 [
°
F]
and
[5]
Ni 1000 [
°
F]
if operating in Fahrenheit.
NOTICE
If the input is not in use, set it for
voltage.
If set for temperature and used as feedback,
set the unit for either Celsius or Fahrenheit.
•
Parameter 20-12 Reference/Feedback
Unit
.
•
Parameter 21-10 Ext. 1 Ref./Feedback
Unit
.
•
Parameter 21-30 Ext. 2 Ref./Feedback
Unit
.
•
Parameter 20-05 Feedback 2 Source
Unit
.
[1]
*
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-01 Terminal X42/3 Mode
Option:
Function:
Terminal X42/3 can be programmed as an
analog input accepting a voltage or input
from either Pt 1000 or Ni 1000 temperature
sensors. Select the mode.
[2] Pt 1000 [
°
C]
and
[4] Ni 1000 [
°
C]
if
operating in Celsius, or
[3] Pt 1000 [
°
F]
and
[5]
Ni 1000 [
°
F]
if operating in Fahrenheit.
NOTICE
If the input is not in use, set it for
voltage.
If set for temperature and used as feedback,
set the unit for either Celsius or Fahrenheit.
•
Parameter 20-12 Reference/Feedback
Unit
.
•
Parameter 21-10 Ext. 1 Ref./Feedback
Unit
.
•
Parameter 21-30 Ext. 2 Ref./Feedback
Unit
.
26-01 Terminal X42/3 Mode
Option:
Function:
•
Parameter 20-05 Feedback 2 Source
Unit
.
[1]
*
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-02 Terminal X42/5 Mode
Option:
Function:
Terminal X42/5 can be programmed as an
analog input accepting a voltage or input
from either Pt 1000 (1000
Ω
at 0
°
C) or Ni
1000 (1000
Ω
at 0
°
C) temperature sensors.
Select the mode.
[2] Pt 1000 [
°
C]
and
[4] Ni 1000 [
°
C]
if
operating in Celsius, or
[3] Pt 1000 [
°
F]
and
[5]
Ni 1000 [
°
F]
if operating in Fahrenheit.
NOTICE
If the input is not in use, set it for
voltage.
If set for temperature and used as feedback,
set the unit for either Celsius or Fahrenheit:
•
Parameter 20-12 Reference/Feedback
Unit
.
•
Parameter 21-10 Ext. 1 Ref./Feedback
Unit
.
•
Parameter 21-30 Ext. 2 Ref./Feedback
Unit
.
•
Parameter 20-05 Feedback 2 Source
Unit
.
[1]
*
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-10 Terminal X42/1 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-31 V]
Enter the low voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
parameter 26-14 Term. X42/1 Low Ref./Feedb.
Value
Parameter Description
VLT
®
AQUA Drive FC 202
218