16-96 Maintenance Word
Range:
Function:
Position
4
⇒
Valve
Fan
bea-
rings
Pump
bea-
rings
Motor
bea-
rings
Position
3
⇒
Pump
seals
Tempe-
rature
trans-
mitter
Flow
trans-
mitter
Pres-
sure
trans-
mitter
Position
2
⇒
Drive
system
health
check
Drive
cooling
fan
Filter
Fan
belt
Position
1
⇒
–
–
–
War-
ranty
0
hex
–
–
–
–
1
hex
–
–
–
+
2
hex
–
–
+
–
3
hex
–
–
+
+
4
hex
–
+
–
–
5
hex
–
+
–
+
6
hex
–
+
+
–
7
hex
–
+
+
+
8
hex
+
–
–
–
9
hex
+
–
–
+
A
hex
+
–
+
–
B
hex
+
–
+
+
C
hex
+
+
–
–
D
hex
+
+
–
+
E
hex
+
+
+
–
F
hex
+
+
+
+
Table 3.27 Maintenance Word
Example:
The preventive maintenance word shows
040Ahex.
Position
1
2
3
4
Hex value
0
4
0
A
Table 3.28 Example
The 1
st
digit 0 indicates that no items from
the 4
th
row require maintenance.
The 2
nd
digit 4 refers to the 3
rd
row indicating
that the frequency converter cooling fan
requires maintenance.
The 3
rd
digit 0 indicates that no items from
the 2
nd
row require maintenance.
The 4
th
digit A refers to the top row
indicating that the valve and the pump
bearings require maintenance.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
155