6-61 Terminal X30/8 Min. Scale
Range:
Function:
0 %
*
[0 -
200 %]
Scales the minimum output of the selected analog
signal on terminal X30/8. Scale the minimum
value as a percentage of the maximum signal
value. For example, enter the value 25% if the
output should be 0 mA at 25% of the maximum
output value. The value can never exceed the
corresponding setting in
if the value is below 100%.
This parameter is active when VLT
®
General
Purpose I/O MCB 101 is mounted in the frequency
converter.
6-62 Terminal X30/8 Max. Scale
Range:
Function:
100
%
*
[0 -
200 %
]
Scales the maximum output of the selected
analog signal on terminal X30/8. Scale the value
to the required maximum value of the current
signal output. Scale the output to give a lower
current than 20 mA at full scale, or 20 mA at an
output below 100% of the maximum signal value.
If 20 mA is the required output current at a value
between 0–100% of the full-scale output,
program the percentage value in the parameter,
that is 50%=20 mA. If a current 4–20 mA is
required at maximum output (100%), calculate
the percentage value as follows:
20 mA/desired maximum current × 100 %
i . e . 10 mA:
20 mA
10 mA × 100 % = 200 %
6-63 Terminal X30/8 Output Bus Control
Range:
Function:
0 %
*
[0 - 100 %] Contains the value to apply to the output
terminal when it is configured as bus-
controlled.
6-64 Terminal X30/8 Output Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] Contains the value to apply to the output
terminal when it is configured as bus-
controlled timeout and timeout is detected.
6-70 Terminal X45/1 Output
Select the output of terminal X45/1 of VLT
®
Extended Relay Card
MCB 113.
Option:
Function:
[0]
*
No operation
[52]
MCO 0-20mA/0-10V
[53]
MCO 4-20mA
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Fe-200%
[103]
Motor cur. 0-Imax
6-70 Terminal X45/1 Output
Select the output of terminal X45/1 of VLT
®
Extended Relay Card
MCB 113.
Option:
Function:
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[108]
-160%
[109]
Out frq 0-Fmax
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[116]
Cascade Reference
[117]
Shaft Power
[118]
Shaft Power 4-20mA
[130]
Out frq 0-100 4-20mA
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.0-lim 4-20 mA
[135]
Torq.0-nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[138]
Torque 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4-20mA
[143]
Ext. CL 1 4-20mA
[144]
Ext. CL 2 4-20mA
[145]
Ext. CL 3 4-20mA
[146]
Cascade Ref. 4-20mA
[147]
Main act val 0-20mA
[148]
Main act val 4-20mA
[150]
Out frq 0-Fmax 4-20mA
[156]
Flow Rate
[157]
Flow Rate 4-20mA
[254]
DC Link 0-20mA
[255]
DC Link 4-20mA
6-71 Terminal X45/1 Min. Scale
Enter the minimum scaling value of output of the analog signal
on terminal X45/1.
Range:
Function:
0 %
*
[0 - 200 %]
6-72 Terminal X45/1 Max. Scale
Enter the maximum scaling value of output of the analog signal
on terminal X45/1.
Range:
Function:
100 %
*
[0 - 200 %]
Parameter Description
VLT
®
AQUA Drive FC 202
98
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02