[19] Freeze ref
Freezes the actual reference. The frozen
reference is now the point of enable/
condition for speed up and speed down to
be used. If speed up/speed down is used,
the speed change always follows ramp 2
(
parameter 3-51 Ramp 2 Ramp Up Time
and
parameter 3-52 Ramp 2 Ramp Down Time
) in
the range 0–
[20] Freeze output Freezes the actual motor frequency (Hz). The
frozen motor frequency is now the point of
enable/condition for speed up and speed
down to be used. If speed up/speed down is
used, the speed change always follows ramp
2 (
parameter 3-51 Ramp 2 Ramp Up Time
and
parameter 3-52 Ramp 2 Ramp Down Time
) in
the range 0–
parameter 1-23 Motor Frequency
.
NOTICE
When
[20] Freeze output
is active, the
frequency converter cannot be
stopped via a low [13] Start signal.
Stop the frequency converter via a
terminal programmed for
[2] Coast
inverse
or
[3] Coast and reset, inverse
.
[21] Speed up
For digital control of the speed up/speed
down (motor potentiometer). Activate this
function by selecting either
[19] Freeze
reference
or
[20] Freeze output
. When
[21]
Speed up
is activated for less than 400 ms,
the resulting reference is increased by 0.1%.
If
[21] Speed up
is activated for more than
400 ms, the resulting reference ramps
according to ramp 1 in
[22] Speed down
Same as
[21] Speed up
.
[23] Set-up select
bit 0
Selects 1 of the 4 set-ups. Set
to Multi Set-up.
[24] Set-up select
bit 1
Same as
[23] Set-up select bit 0
.
(Default digital input 32).
[32] Pulse input
Select
[32] Pulse input
when using a pulse
sequence as either reference or feedback.
Scaling is done in
parameter group 5-5* Pulse
Input
.
[34] Ramp bit 0
Select which ramp to use. Logic 0 selects
ramp 1 while logic 1 selects ramp 2.
[36] Mains failure
inverse
Activates
.
Mains failure inverse is active in the logic 0
situation.
[42] Ref source bit
0
An active input in bit 0 selects AI54 as the
reference source (see
parameter group 3-1*
References
, option
[35] Digital input select
).
An inactive input selects AI53.
[51] Hand/Auto
Start
Selects hand or auto start. High signal
selects auto on only, Low signal selects hand
on only.
[52] Run
Permissive
The input terminal, for which the
[52] Run
Permissive
has been programmed, must be
logic 1 before a start command can be
accepted. Run permissive has a logic AND
function related to the terminal, which is
programmed for
[8] Start
,
[14] Jog
, or
[20]
Freeze Output
. To start running the motor,
both conditions must be fulfilled. If
[52] Run
Permissive
is programmed on multiple
terminals, it only has to be logic 1 on 1 of
the terminals to carry out the function. The
digital output signal for run request (
[8]
Start
,
[14] Jog
, or
[20] Freeze output
)
programmed in
parameter group 5-3* Digital
Outputs
, or
parameter group 5-4* Relays
, is
not affected by
[52] Run Permissive
.
[53] Hand start
A signal applied puts the frequency
converter into hand-on mode as if [Hand
On] has been pressed and a normal stop
command is overridden. If disconnecting the
signal, the motor stops. To make any other
start commands valid, assign another digital
input to
[54] Auto Start
and apply a signal to
this. [Hand On] and [Auto On] have no
impact. [Off] overrides local start and auto
start. Press either [Hand On] or [Auto On] to
make local start and auto start active again.
If there is no signal on neither
[53] Hand
start
nor
[54] Auto start
, the motor stops
regardless of any normal start command
applied. If a signal is applied to both
[53]
Hand start
and
[54] Auto start
, the function is
auto start. If pressing [Off], the motor stops
regardless of signals on
[53] Hand start
and
[54] Auto start
.
[54] Auto start
A signal applied puts the frequency
converter into auto-on mode as if [Auto On]
has been pressed. See also
[53] Hand Start
.
[55] DigiPot
Increase
Uses the input as an increase signal to the
digital potentiometer function described in
parameter group 3-9* Digital Pot.Meter
.
[56] DigiPot
Decrease
Uses the input as a decrease signal to the
digital potentiometer function described in
parameter group 3-9* Digital Pot.Meter
.
[57] DigiPot Clear
Uses the input to clear the digital potenti-
ometer reference described in
parameter
group 3-9* Digital Pot.Meter
.
[60] Counter A
(up)
(Terminal 29 or 33 only) Input for increment
counting in the SLC counter.
[61] Counter A
(down)
(Terminal 29 or 33 only) Input for decrement
counting in the SLC counter.
[62] Reset Counter
A
Input for reset of counter A.
[63] Counter B
(up)
(Terminal 29 and 33 only) Input for
increment counting in the SLC counter.
[64] Counter B
(down)
(Terminal 29 and 33 only) Input for
decrement counting in the SLC counter.
Parameter Description
VLT
®
AQUA Drive FC 202
78
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3