10-11 Process Data Config Write
Option:
Function:
[411]
Motor Speed Low Limit [RPM]
[412]
Motor Speed Low Limit [Hz]
[413]
Motor Speed High Limit [RPM]
[414]
Motor Speed High Limit [Hz]
[416]
Torque Limit Motor Mode
[417]
Torque Limit Generator Mode
[553]
Term. 29 High Ref./Feedb. Value
[558]
Term. 33 High Ref./Feedb. Value
[590]
Digital & Relay Bus Control
[593]
Pulse Out #27 Bus Control
[595]
Pulse Out #29 Bus Control
[597]
Pulse Out #X30/6 Bus Control
[615]
Terminal 53 High Ref./Feedb. Value
[625]
Terminal 54 High Ref./Feedb. Value
[653]
Terminal 42 Output Bus Control
[663]
Terminal X30/8 Output Bus Control
[673]
Terminal X45/1 Bus Control
[683]
Terminal X45/3 Bus Control
[894]
Bus Feedback 1
[895]
Bus Feedback 2
[896]
Bus Feedback 3
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1685] FC Port CTW 1
[1686] FC Port REF 1
10-12 Process Data Config Read
Option: Function:
Select the process read data for I/O assembly instances
101/151. Elements 2 and 3 of this array can be selected.
Elements 0 and 1 of the array are fixed.
10-13 Warning Parameter
Range:
Function:
0
*
[0 - 65535 ] View a DeviceNet-specific warning word. One
bit is assigned to every warning. Refer to the
VLT
®
MCA 104 DeviceNet Installation Guide
for
further information.
Bit
Description
0
Bus not active.
1
Explicit connection timeout.
2
I/O connection.
3
Retry limit reached.
4
Actual is not updated.
5
CAN bus off.
6
I/O send error.
7
Initialization error.
8
No bus supply.
9
Bus off.
10
Error passive.
11
Error warning.
Bit
Description
12
Duplicate MAC ID error.
13
RX queue overrun.
14
TX queue overrun.
15
CAN overrun.
Table 3.20 Warning Bits
10-14 Net Reference
Read only from LCP.
Option: Function:
Select the reference source in instances 21/71 and
20/70.
[0]
*
Off Enables reference via analog/digital inputs.
[1]
On Enables reference via the fieldbus.
10-15 Net Control
Read only from LCP.
Option: Function:
Select the control source in instances 21/71 and 20/70.
[0]
*
Off Enables control via analog/digital inputs.
[1]
On Enable control via the fieldbus.
3.11.3 10-2* COS Filters
10-20 COS Filter 1
Range:
Function:
0
*
[0 -
65535 ]
Enter the value for COS filter 1 to set up the
filter mask for the status word. When operating
in COS (change-of-state), this function filters
out bits in the status word that should not be
sent if they change.
10-21 COS Filter 2
Range:
Function:
0
*
[0 -
65535 ]
Enter the value for COS filter 2 to set up the
filter mask for the Main Actual Value. When
operating in COS, this function filters out bits in
the main actual value that should not be sent if
they change.
10-22 COS Filter 3
Range:
Function:
0
*
[0 - 65535 ] Enter the value for COS filter 3 to set up the
filter mask for PCD 3. When operating in COS,
this function filters out bits in PCD 3 that
should not be sent if they change.
Parameter Description
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
111
3
3