8-52 DC Brake Select
Option:
Function:
NOTICE
Only selection
[0] Digital Input
is available
when
parameter 1-10 Motor Construction
is
set to
[1] PM, non-salient SPM
.
[0] Digital
input
Activates start command via a digital input.
[1] Bus
Activates start command via the serial communi-
cation port or fieldbus option.
[2] Logic
AND
Activates start command via the fieldbus/serial
communication port AND via 1 of the digital
inputs.
[3] Logic OR Activates start command via the fieldbus/serial
communication port OR via 1 of the digital inputs.
8-53 Start Select
Select the trigger for the start function.
Option:
Function:
[0]
Digital input A digital input triggers the start function.
[1]
Bus
A serial communication port or the fieldbus
triggers the start function.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the start function.
[3]
*
Logic OR
The fieldbus/serial communication port or a
digital input triggers the start function.
8-54 Reversing Select
Select control of the frequency converter reverse function via the
terminals (digital input) and/or via the fieldbus.
Option:
Function:
NOTICE
This parameter is active only when
is set to
[0]
Digital and control word
.
[0]
*
Digital input Activates reverse command via a digital input.
[1]
Bus
Activates reverse command via the serial
communication port or fieldbus option.
[2]
Logic AND
Activates reverse command via the fieldbus/
serial communication port and via 1 of the
digital inputs.
[3]
Logic OR
Activates reverse command via the fieldbus/
serial communication port or via 1 of the
digital inputs.
Parameter Description
VLT
®
AQUA Drive FC 202
108
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02