3.14 Parameters 15-** Drive Information
Parameter group containing frequency converter
information such as operating data, hardware configu-
ration, and software versions.
3.14.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is
turned off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 -
2147483647 h]
View how many hours the motor has run.
Reset the counter in
parameter 15-07 Reset Running Hours
Counter
. The value is saved when the
frequency converter is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
*
[0 -
2147483647
kWh]
Register the power consumption of
the motor as an average value over 1
hour. Reset the counter in
parameter 15-06 Reset kWh Counter
.
15-03 Power Up's
Range:
Function:
0
*
[0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
temperature faults.
15-05 Over Volt's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
overvoltages.
15-06 Reset kWh Counter
Option:
Function:
[0]
*
Do not reset
No reset of the kWh counter is required.
[1]
Reset counter Press [OK] to reset the kWh counter to 0
(see
).
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not
reset
No reset of the running hours counter is
required.
[1]
Reset
counter
Select
[1] Reset counter
and press [OK] to reset
the running hours counter
(
) and
parameter 15-08 Number of Starts
to 0 (see
also
15-08 Number of Starts
Range:
Function:
0
*
[0 -
2147483647 ]
NOTICE
This parameter is reset when resetting
parameter 15-07 Reset Running Hours
Counter
This is a readout parameter only. The
counter shows the number of starts and
stops caused by a normal start/stop
command and/or when entering/leaving
sleep mode.
3.14.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (
parameter 15-10 Logging Source
) at individual rates
parameter 15-11 Logging Interval
). A trigger event
) and window
parameter 15-14 Samples Before Trigger
) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
Function:
[0]
*
None
[1472]
VLT Alarm Word
[1473]
VLT Warning Word
[1474]
VLT Ext. Status Word
[1600]
Control Word
[1601]
Reference [Unit]
[1602]
Reference %
[1603]
Status Word
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor Current
[1616]
Torque [Nm]
[1617]
Speed [RPM]
[1618]
Motor Thermal
[1622]
Torque [%]
[1625]
Torque [Nm] High
[1630]
DC Link Voltage
Parameter Description
Programming Guide
MG20OB02