2.2.1 The LCP Display
The LCP display has backlight and a total of 6 alpha-
numeric lines. The display lines show the direction of
rotation (arrow), the selected set-up, and the programming
set-up. The display is divided into 3 sections.
Top section
Shows up to 2 measurements in normal operating status.
Middle section
The top line shows up to 5 measurements with related
units, regardless of status (except if there is an alarm/
warning).
Bottom section
Always shows the state of the frequency converter in
Status
mode.
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A
25.3kW
1(1)
130BP074.10
!
Illustration 2.2 Bottom Section
The active set-up (selected as the active set-up in
parameter 0-10 Active Set-up
) is shown. When programming
another set-up than the active set-up, the number of the
programmed set-up appears to the right.
Display contrast adjustment
Press [Status] and [
▲
] for darker display.
Press [Status] and [
▼
] for brighter display.
Most parameter set-ups can be changed immediately via
the LCP, unless a password has been created via
parameter 0-60 Main Menu Password
or via
parameter 0-65 Quick Menu Password
.
Indicator lights
If certain threshold values are exceeded, the alarm and/or
warning indicator lights up. A status and an alarm text
appear on the LCP.
The ON indicator light is activated when the frequency
converter receives mains voltage, or via a DC bus terminal,
or a 24 V external supply. At the same time, the backlight
is on.
•
Green LED/On: Control section is working.
•
Yellow LED/Warn.: Indicates a warning.
•
Flashing red LED/Alarm: Indicates an alarm.
On
Warn.
Alarm
130BP044.10
Illustration 2.3 Indicator Lights
LCP keys
The control keys are divided into functions. The keys below
the display and indicator lights are used for parameter set-
up, including the option of display indication during
normal operation.
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
Illustration 2.4 LCP Keys
[Status]
Indicates the status of the frequency converter and/or the
motor. Select between 3 different readouts by pressing
[Status]: 5-line readouts, 4-line readouts, or smart logic
control.
Press [Status] to select the mode of display or to return to
display mode from either the
Quick Menu
mode, the
Main
Menu
mode, or
Alarm
mode. Also use [Status] to toggle
single or double readout mode.
[Quick Menu]
Provides quick access to the most common functions of
the frequency converter.
The [Quick Menu] consists of:
•
Q1: My personal menu.
•
Q2: Quick set-up.
•
Q3: Function set-ups.
•
Q4: SmartStart.
•
Q5: Changes made.
•
Q6: Loggings.
•
Q7: Water and pumps.
How to Program
VLT
®
AQUA Drive FC 202
14
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
2
2
Содержание VLT AQUA Drive FC 202