0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 -
255 ]
View a list of all the set-ups linked by
parameter 0-12 This Set-up Linked to
. The parameter
has 1 index for each parameter set-up. The value
for each index shows which set-ups are linked to
that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 3.2 Set-up Link Example
0-14 Readout: Prog. Set-ups / Channel
Range:
Function:
0
*
[-2147483648
- 2147483647 ]
View the setting of
parameter 0-11 Programming Set-up
for each
of the 4 different communication channels.
When the number is shown in hex, as it is in
the LCP, each number shows 1 channel.
Numbers 1–4 show a set-up number; F
stands for the factory setting, and A stands
for an active set-up. The channels are, from
right to left: LCP, fieldbus, USB, HPFB1.5.
Example: The value AAAAAA21h means that
the fieldbus channel uses set-up 2 in
parameter 0-11 Programming Set-up
, the LCP
uses set-up 1, and all other channels use the
active set-up.
3.2.3 0-2* LCP Display
Define the variables shown in the LCP.
NOTICE
For information on how to write display texts, refer to:
•
.
•
.
•
.
0-20 Display Line 1.1 Small
Option:
Function:
Select a variable to show in line 1, left
position.
[0]
None
No display value selected
[953]
Profibus
Warning Word
Shows PROFIBUS communication
warnings.
0-20 Display Line 1.1 Small
Option:
Function:
[1005] Readout
Transmit Error
Counter
Shows the number of CAN control
transmission errors since the last power-
up.
[1006] Readout
Receive Error
Counter
Shows the number of CAN control
receipt errors since the last power-up.
[1007] Readout Bus
Off Counter
Shows the number of bus-off events
since the last power-up.
[1013] Warning
Parameter
Shows a DeviceNet-specific warning
word. One separate bit is assigned to
every warning.
[1230] Warning
Parameter
[1472] VLT Alarm
Word
[1473] VLT Warning
Word
[1474] VLT Ext. Status
Word
[1501] Running Hours View the number of running hours of
the motor.
[1502] kWh Counter
View the mains power consumption in
kWh.
[1600] Control Word
View the control word sent from the
frequency converter via the serial
communication port in hex code.
[1601] Reference
[Unit]
Total reference (sum of digital, analog,
preset, bus, freeze reference, catch up,
and slow down) in selected unit.
[1602] Reference %
Total reference (sum of digital, analog,
preset, bus, freeze reference, catch up,
and slow down) in percent.
[1603] Status Word
Present status word.
[1605] Main Actual
Value [%]
One or more warnings in hex code.
[1609] Custom
Readout
View the user-defined readouts as
defined in:
•
Parameter 0-30 Custom Readout
Unit
•
Parameter 0-31 Custom Readout
Min Value
.
•
Parameter 0-32 Custom Readout
Max Value
[1610] Power [kW]
Actual power consumed by the motor
in kW.
[1611] Power [hp]
Actual power consumed by the motor
in hp.
[1612] Motor Voltage
Voltage supplied to the motor.
Parameter Description
VLT
®
AQUA Drive FC 202
30
Danfoss A/S © 05/2018 All rights reserved.
MG20OB02
3
3