4.1.6 4-** Limits/Warnings
Param-
eter #
Parameter description
Default value
4 set-up
Change during
operation
Conversion
index
Type
4-1* Motor Limits
4-10
Motor Speed Direction
[0] Clockwise
All set-ups
FALSE
-
Uint8
4-11
Motor Speed Low Limit [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-12
Motor Speed Low Limit [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-13
Motor Speed High Limit [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-14
Motor Speed High Limit [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-16
Torque Limit Motor Mode
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-17
Torque Limit Generator Mode
100%
All set-ups
TRUE
-1
Uint16
4-18
Current Limit
ExpressionLimit
All set-ups
TRUE
-1
Uint32
4-19
Max Output Frequency
ExpressionLimit
All set-ups
FALSE
-1
Uint16
4-5* Adj. Warnings
4-50
Warning Current Low
0 A
All set-ups
TRUE
-2
Uint32
4-51
Warning Current High
ImaxVLT (P1637)
All set-ups
TRUE
-2
Uint32
4-52
Warning Speed Low
0 RPM
All set-ups
TRUE
67
Uint16
4-53
Warning Speed High
outputSpeed-
HighLimit (P413)
All set-ups
TRUE
67
Uint16
4-54
Warning Reference Low
-999999.999 N/A
All set-ups
TRUE
-3
Int32
4-55
Warning Reference High
999999.999 N/A
All set-ups
TRUE
-3
Int32
4-56
Warning Feedback Low
-999999.999
ReferenceFeed-
backUnit
All set-ups
TRUE
-3
Int32
4-57
Warning Feedback High
999999.999
ReferenceFeed-
backUnit
All set-ups
TRUE
-3
Int32
4-58
Missing Motor Phase Function
[2] Trip 1000 ms
All set-ups
TRUE
-
Uint8
4-6* Speed Bypass
4-60
Bypass Speed From [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-61
Bypass Speed From [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-62
Bypass Speed To [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-63
Bypass Speed To [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-64
Semi-Auto Bypass Set-up
[0] Off
All set-ups
FALSE
-
Uint8
Parameter Lists
Programming Guide
MG20OB02
Danfoss A/S © 05/2018 All rights reserved.
255