CTC EcoZenith i350
If a CTC VT 80 volume tank is installed to increase flow, the flow between
the heat pump and CTC VT 80 is calculated according to the flow below.
CTC EcoAir 406
0.21 l/s
CTC EcoAir 408
0.27 l/s
CTC EcoAir 510
0.21 l/s
CTC EcoAir 520
0.39 l/s
CTC EcoPart 406
0.14 l/s
CTC EcoPart 408
0.20 l/s
CTC EcoPart 410
0.24 l/s
CTC EcoPart 412
0.28 l/s
This building
requires:
l/s between heat pump and CTC VT
80.
This building
requires:
l/s to the heating circuit
Example: House with 11 kW floor heating where an EcoAir 510 is to be
installed.
The heating circuit requires a flow of 0.53 l/s. External circulation pump G1 is
designed for this flow. The heat pump requires a flow of 0.21 l/s.
Step 5 Set % of PWM signal on the charge pump
Use the pump and pressure differential diagram overleaf to determine the
speed [%] according to which the circulation pump/charge pump should be
set.