110
CTC EcoZenith i350
Alarm messages
Description
[E035] High pressure switch
The refrigerant’s high pressure switch has been triggered. Press reset and
check whether the alarm recurs. If the fault recurs, contact your installer.
[E040] Low brine flow
Low brine flow is often caused by air in the collector system, especially
immediately following installation. Collectors which are too long can also be a
cause. Press reset and check whether the alarm recurs. Also check the brine
filter that has been installed.
If the fault recurs, contact your installer.
[E041] Low brine temp.
Incoming brine temperatures from the bore hole/ground coil are too low. Press
reset and check whether the alarm recurs. If the fault recurs, contact your
installer to check the positioning of the cold side.
[E044] Stop, high comp. temp.
This message appears when the compressor temperature is high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E045] Stop, low evaporation
This message appears when the evaporation temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E046] Stop, high evaporation
This message appears when the evaporation temperature is high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E047] Stop, low suct. gas exp.
valve
This message appears when the suction gas temperature is low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E048] Stop, low evap. exp.
valve
This message appears when the expansion valve’s evaporation temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E049] Stop, high evap. exp.
valve
This message appears when the expansion valve’s evaporation temperature is
high.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E050] Stop, low overheat. exp.
valve
This message appears when the expansion valve’s overheat temperature is
low.
Press reset and check whether the alarm recurs. If the fault recurs, contact
your installer.
[E052] Phase 1 missing
[E053] Phase 2 missing
[E054] Phase 3 missing
This message appears in the event of a phase failure.
[E055] Incorrect phase
sequence
The product’s compressor motor must rotate in the right direction. The
product checks that the phases are connected correctly; otherwise, an alarm
is triggered. This will require changing two of the phases into the product. The
power supply to the system must be shut off when rectifying this fault. This
fault generally only occurs during installation.
Содержание EcoZenith i350 H
Страница 4: ...4 CTC EcoZenith i350...
Страница 27: ...27 CTC EcoZenith i350...
Страница 29: ...29 CTC EcoZenith i350...
Страница 30: ...30 CTC EcoZenith i350 X2 6 4 Wiring diagram CTC EcoZenith i350 3x400V...
Страница 32: ...32 CTC EcoZenith i350 X2 6 5 Wiring diagram CTC EcoZenith i350 1x230V...
Страница 34: ...34 CTC EcoZenith i350 X2 6 6 Wiring diagram CTC EcoZenith i350 3x230V...
Страница 105: ...105 CTC EcoZenith i350...
Страница 115: ......
Страница 116: ...Enertech AB P O Box 309 SE 341 26 Ljungby Sweden www ctc se www ctc heating com 162 205 22 2 2017 11 14...