Installation and Setup
X-320M™ User's Manual
Logging Rate
This field is used to specify the time period of logging. A numerical value is entered into the text
field, and the unit of time is selected using the adjacent radio buttons. Time units are
Minutes
,
Hours
, and
Days
. The range of values in this field is
1
to
20864
. The default setting for this field is
60
. Periodic logging can be disabled by selecting the Event Logging Only radio button.
Logging Configuration
This table is used to select which sensors get logged and which events trigger the logging. The first
column in the table identifies the sensor(s) that can be logged or cause logging events. The second
column is used to specify what gets logged. The third column is used to specify which events can
cause a log entry to be created. The last column is used to specify the Trigger Delta for the
corresponding sensors.
When sensors and/or Vin are selected as an
Event Trigger
, logging will occur whenever the input
or sensor changes by the trigger delta. All sensors can be configured to trigger a log entry to be
created. The Wind Gust is the only log option that can trigger logging to occur without a specific
delta value. When Wind Gust is configured to trigger logging, any registered wind gust will create a
new log entry.
Next Log Time
This field displays the next periodic log time. If logging is disabled, the Next Log Time will indicate
"Disabled."
Note: This information is updated only when the page is refreshed.