X-320M™ User's Manual
Installation and Setup
High Alarm
This setting is used to set the trigger point for a high alarm condition. The alarm is triggered when
the value at the sensor exceeds the High Alarm Value. The default High Alarm is
20
.
Low Alarm
This setting is used to set the trigger point for a low alarm condition. The alarm is triggered when the
value at the sensor drops below the Low Alarm Value. The default Low Alarm is
10
.
Deadband
The Deadband prevents alarms from triggering excessively when the sensor measurement
vacillates around the trigger point.
With High Alarms, the measurement must fall below the High Alarm point minus the Deadband
before the High Alarm will be triggered again. Likewise, the Deadband on the Low Alarm requires
the measurement to rise above the Low Alarm point plus the deadband before the Low Alarm will be
triggered again.
For example, if the Deadband is set to .5 inHg, and a High Alarm occurs at 31 inHg, the alarm will
not trigger again until the barometric pressure first drops below 30.5 inHg (31 - 0.5 inHg), as shown
in the figure below. The default Deadband is _____. This can be set from _____ to ______.
Email Option
Simple email messages can be sent in response to alarm conditions. This parameter is used to
specify what alarm conditions, if any, will cause email messages to be sent. Email notification will
work only if email is correctly set up in the
Network
setup page.
-
No Email Messages
:
No email messages will be sent due to alarm conditions.
-
Send Email on High Alarm
: Email notifications will be sent due to the High Alarm condition.
-
Send Email on Low Alarm
:
Email notifications will be sent due to the Low Alarm condition.
-
Send Email on High and Low Alarm
:
Email notifications will be sent due to the High and/or
Low Alarm condition.
-
Send Email on High, Low, and Normal
:
Email notifications will be sent due to the High
Alarm, Low Alarm, or when Normal conditions are regained.
Use Email Address
If email messages are to be sent based on alarm conditions, these check boxes specify to which
email addresses the message will be sent. Email addresses specified on the
Network
setup tab will
Xytronix Research & Design, Inc.
Page 81
Figure 2.4w - Barometric Pressure Alarm Deadband