X-320M™ User's Manual
Appendix G: Common Sensor Setup Parameters
Humidity
X-320M™ can be used with 1-Wire humidity/temperature sensor such as Xytronix X-DTHS-WM. Linear
response analog sensors (voltage or current output) may also be used. Non-linear thermistors are not
compatible.
The use of 1-Wire sensors has the advantage of allowing multiple sensors to be installed and frees up
analog ports for other sensor options.
Make
Model
Output
Slope
Offset
Connections
Xytronix
X-DTHS-S12 1-Wire
F: 1.0
C: 0.5555
F: 0
C: 17.778
5Vout
Gnd
Data
RM Young
41382VC
0-5 VDC
%RH: 20
0
5Vref
Agnd
Ain
RM Young
41382VF
0-5 VDC
%RH: 20
0
5Vref
Agnd
Ain
Radiation shields such as the Davis Instruments 7714 or RM Young 41003 may be required.
The RM Young sensors are often listed as 0-1 VDC output. These sensors have a selectable output
range and can be configured as 0-5 VDC. Please refer to the sensor instruction sheet.
Solar Radiation
Solar radiation sensors can be installed on the analog input ports.
Make
Model
Output
Slope
Offset
Connections
Apogee
Instruments
SP-215
0-5 VDC
W/m^2: 250
0
5Vout
Gnd
Data
Met One
096
0-5 VDC
W/m^2: 125000 0
5Vref
Agnd
Ain
Xytronix Research & Design, Inc.