Installation and Setup
X-320M™ User's Manual
and devices from other manufacturers. This is enabled by selecting
Yes
in this field. The default
setting for this field is
No.
(See
3.4 Modbus Operation
for more information on using X-320M™ on
a Modbus network.)
Note: Modbus communications are disabled whenever the Control Password is enabled.
Modbus Port
This specifies the port used for Modbus/TCP communications with X-320M™. By default this is set
to port 502 which is the standard Modbus port. It can be set within the range of 0 to 65535.
Big Endian
32-bit data is treated as two individual 16-bit words using IEEE 754 floating point format. Floating
point format is used for sensor, pulse counter, analog, and frequency data as well as for setting
output pulse duration.
If the checkbox is set, the X-320™ will use big-endian architecture, and the most significant 16-bit
word (big end) is sent first. If the box is cleared, then the X-320™ will use little-endian architecture,
and the least significant word (little end) is sent first. The default setting for this box is
unchecked,
use little-endian.
For example, in little-endian format, a 32-bit floating point number represented by '1234 ABCD' is
sent as 'ABCD 1234'.
Remote Services Enabled
This option enables or disables Remote Services. If
Yes
is selected, Remote Services will be
enabled as soon as the submit button is pressed and X-320M™ will immediately attempt to make a
connection with the remote server (power cycle not required). Once a connection is established, the
connection will remain until it is disconnected by the remote server. Proper connection with the
remote server can be verified by viewing the system status log file (see
Appendix E: Log Files
).
The default setting for this field is
No
. Most users should leave this setting at its default. (See
Remote Services
at the end of this section
for more information.)
Server Name/IP Address
Specify the name or IP address of the Remote Services server here. If the IP address is specified,
enter it in the format aaa.bbb.ccc.ddd. For numbers that are less than 100, preceding zeros should
not be included (for example, enter 80 rather than 080). This field can be up to 40 characters long
and has no default setting.
Server Port
Enter the TCP port used for the Remote Services server. This can be set within the range of 0-
65535. The default setting for this field is 8000.
Connection String
This text is sent to the Remote Services server when the connection is established. This string
should include any information required by the server at connection. For example, it may include an
ID number, customer number, password, etc. The format is entirely dependent upon the server
requirements. This field can be up to 80 characters long. Default text is provided only as an example
placeholder. The default text is [<
Serial Number
>]:ControlByWeb,METSTN.
Connection Interval
This field specifies the periodic interval in which X-320M™ attempts to connect to the remote server,
or if X-320M™ is already connected, it is the interval in which X-320M™ sends the connection
string. This field can be set within the range of 1 to 34452 minutes. The default setting for this field is
1 minute.
SNMP Enabled
When this option is set to
Yes
, X-320M™ will support SNMP. The default setting for this option is
No
. (See
Appendix I
for more information.)