X-320M™ User's Manual
Installation and Setup
triggered again.
For example, if the deadband is set to 50, and a High Alarm occurs at 300 W/m
2
, the alarm will not
trigger again until the Solar Radiation first drops below 250 W/m
2,
(300 W/m
2,
- 50 W/m
2,
), as shown
in the figure below. The default Deadband is
0.50
.
Email Option
Simple email messages can be sent in response to alarm conditions. This parameter is used to
specify what alarm conditions, if any, will cause email messages to be sent. Email notification will
work only if email is correctly set up in the
Network
setup page.
-
No Email Messages
:
No email messages will be sent due to alarm conditions.
-
Send Email on High Alarm
: Email notifications will be sent due to the High Alarm condition.
-
Send Email on Low Alarm
:
Email notifications will be sent due to the Low Alarm condition.
-
Send Email on High and Low Alarm
:
Email notifications will be sent due to the High and/or
Low Alarm condition.
-
Send Email on High, Low, and Normal
:
Email notifications will be sent due to the High
Alarm, Low Alarm, or when Normal conditions are regained.
Use Email Address
If email messages are to be sent based on alarm conditions, these check boxes specify to which
email addresses the message will be sent. Email addresses specified on the
Network
setup tab will
be shown next to each check box.
Xytronix Research & Design, Inc.
Page 77
Figure 2.4u -Solar Radiation Alarm Deadband