Appendix B: Installing New Firmware
Appendix B.1).
4.
Within the ControlByWeb™ Programmer utility programmer, select File, then Open. Specify the firmware
image downloaded from the ControlByWeb™ web site.
Device Upgrade Procedure
Carefully follow the following steps to put X-320M™ into bootloader mode and perform the upgrade:
1.
Remove DC power from X-320M™.
2.
Using a small, non-conductive tool, press and hold the reset button.
3.
While holding the reset button, apply power to X-320M™. The LINK and ACT lights will flash. Continue to
hold the reset button for the next step.
4.
While holding the reset button, press the Upload Firmware button at the bottom of the ControlByWeb™
Programmer window. After the programming process begins, the reset button can be released
5.
Programming will take approximately 20-30 seconds. The LINK LED will stop flashing and remain lit
during this time. X-320M™ will be set to factory defaults with an IP address of 192.168.1.2.
6.
Refer to section
2.3 Establishing Communication for Setup
to reconfigure the X-320M™. Verify the
new version of firmware has been installed by viewing the default
Setup Page
with a web browser
(http://192.168.1.2/setup.html).
Xytronix Research & Design, Inc.
Page 105
Figure Appendix B.2 - Firmware Update Complete