Chapter 6 P0 group basic function
55
t1
Ourput frequency
Hz
Setting frequency
Set acceleration time
Acceleration deceleration
reference frequency
Actual acceleration time
Actual
deceleration time
Set deceleration time
t2
Time
t
6-1 Acceleration and deceleration time
The inverter provides 4 sets of acceleration/deceleration time (P8-03~P8-08), and the user
can switch from the input terminal.
P0-19
Acceleration/decelera
tion unit
0
:
1s
1
:
0.1s
2
:
0.01s
Default
:
1
Used to set 3 acceleration and deceleration time units, which are 1 second, 0.1
second and 0.01 second respectively.
。
Note: After modifying this parameter, the decimal places displayed in each
acceleration/deceleration time will change, and the corresponding
acceleration/deceleration time will also change.
。
P0-21
Auxiliary
frequency
source
offset
frequency
when
superimposing
0.00Hz
~
Maximum frequency P0-10
Default
:
0.00Hz
When the frequency source is used as the main auxiliary operation, P0-21 is used as
the offset frequency, and the result of the main and auxiliary operations is
superimposed as the final frequency setting value, so that the frequency setting can
be more flexible
。
P0-22
Frequency command
resolution
1
:
0.1Hz
2
:
0.01Hz
Default
:
2
This parameter is used to determine the resolution of all frequency-dependent function
codes.
When the frequency resolution is 0.1Hz, the maximum output frequency can reach
3200Hz.
When the frequency resolution is 0.01 Hz, the maximum output frequency is 600.00
Hz.
。
Note: When modifying the function parameters, the decimal places of all frequency-
related parameters will change and the corresponding frequency values will also
change.