Chapter 5 Function parameter
32
P9-09
Number of automatic
resets
0
~
20
0
〇
P9-10
Fault DO action
selection during
automatic fault reset
0
:
no act
1
:
act
0
〇
P9-11
Fault auto reset
interval
0.1s
~
100.0s
1.0s
〇
P9-12
Input phase loss /
contactor suction
protection option
Unit’s
:
Input phase loss protection option
Ten’s
:
Contactor suction protection option
0: Disable 1: Allow
11
〇
P9-13
Output phase loss
protection option
0: Disable 1: Allow
1
〇
P9-14
First failure type
0: no fault
2: accelerated overcurrent
3: Deceleration over current
4: Constant speed over current
5: Accelerated overvoltage
6: Deceleration overvoltage
7: Constant speed overvoltage
8: Buffer resistor overload
9: Under voltage
10: Inverter overload
11: Motor overload
12: Input phase loss
-
×
P9-15
Second failure type
13: Output phase loss
14: Module overheating
15: External fault
16: Communication error
17: Contactor abnormality
18: Abnormal current detection
19: Tuning error
20: PG card is abnormal
21: Parameter read and write error
22: Inverter hardware is abnormal
23: Motor short circuit to ground
24: Reserved
-
×
P9-16
Third (most recent)
fault type
26: Run time arrives
27: User Defined Fault 1
28: User-defined fault 2
29: Power on time arrives
30: Offload
31: Loss of PID feedback at runtime
40: Fast current limit timeout
41: Switching motor during operation
42: Speed deviation is too large
43: Motor overspeed
45: Motor overheating
51: Initial position error
-
×
P9-17
Frequency at the third
failure
-
-
×
P9-18
Current at the third
fault
-
-
×
P9-19
Bus voltage at the third
fault
-
-
×