Chapter 5 Function parameter
31
P8-40
Arbitrary arrival current 2
0.0%
~
300.0%
(
Motor rated
current
)
100.0%
〇
P8-41
Arbitrary current 2 width
0.0%
~
300.0%
(
Motor rated
current
)
0.0%
〇
P8-42
Timing function selection
0:Invalid
1:Valid
0
●
P8-43
Timing run time selection
0
:
P8-44 setting
1
:
AI1
2
:
AI2
3
:
AI3
Analog input range corresponding P8-
44
0
●
P8-44
Timed running time
0.0Min
~
6500.0Min
0.0Min
●
P8-45
AI1 input voltage protection
value lower limit
0.00V
~
P8-46
3.10V
〇
P8-46
AI1 input voltage protection
value upper limit
P8-45
~
10.00V
6.80V
〇
P8-47
Module temperature
reached
0
℃~
100
℃
75
℃
〇
P8-48
Cooling fan control
0: The fan is running during operation
1: The fan is always running
0
〇
P8-49
Wake-up frequency
Sleep frequency
(
P8-51
)~
Maximum frequency
(
P0-10
)
0.00Hz
〇
P8-50
Wake-up delay time
0.0s
~
6500.0s
0.0s
〇
P8-51
Sleep frequency
0.00Hz
~
Wake-up frequency
(
P8-
49
)
0.00Hz
〇
P8-52
Sleep delay time
0.0s
~
6500.0s
0.0s
〇
P8-53
This run arrival time setting
0.0Min
~
6500.0Min
0.0Min
●
P8-54
Output power correction
factor
0.00%
~
200.0%
100.0%
〇
P9 Group Failure and protection
function
code
Parameter Name
Setting Range
Default Prop
erty
P9-00
Motor overload
protection option
0: Not allow 1: Allow
1
〇
P9-01
Motor overload
protection gain
0.20
~
10.00
1.00
〇
P9-02
Motor overload
warning coefficient
50%
~
100%
80%
〇
P9-07
Power-on short circuit
protection option
0
:
Invalid 1
:
Valid
1
〇
P9-08
Brake unit action
starting voltage
200.0~2000.0V
Model dependent
220V
:
360V
380V
:
690V
480V
:
800V
690V
:
1160V
1140V
:
1850V
〇