Chapter 5 Function parameter
18
Chapter 5 Function parameter
PP-00 is set to a non-zero value, that is, the parameter protection password is set. The
parameter menu must be entered after the password is entered correctly. To cancel the
password, set PP-00 to 0.
“
〇
”: Indicates that this parameter can be changed while the inverter is running or stopped.
“●”: Indicates that this parameter cannot be changed while the inverter is running.
“×”: Indicates that this parameter is only the actual detected record value and cannot be
changed.
5-1 Basic function parameter
P0 Basic function parameter
Function
code
Parameter Name
Setting Range
Default Proper
ty
P0-00
GP type
1
:
G
(
Constant torque load model
)
2
:
P
(
Fan, pump type load model
)
1
×
P0-01
Speed control mode
selection
0
:
Speed sensorless vector control
(
SVC
)
1
:
Speed sensor vector control
(
FVC
)
2
:
V/F control
0
●
P0-02
Run command source
selection
0
:
Operation panel command channel
(
LED close
)
1
:
Terminal command channel
(
LED
open
)
2
:
Communication command channel
(
LED Flashing
)
0
〇
P0-03
Main frequency
source X selection
0
:
Digital setting
(
UP/DOWN
)
non-
record at power failure
1
:
Digital setting
(
UP/DOWN
)
record at
power failure
2
:
AI1
3
:
AI2
4: panel potentiometer
5: Pulse setting (X6)
6: Multi-segment instruction
7: Simple PLC
8: PID
9: Communication given
0
●
P0-04
Auxiliary frequency
source Y selection
Same as P0-03 (main frequency source X
selection)
0
●
P0-05
Frequency offset of
auxiliary frequency
source for X operation
0: relative to the maximum frequency 1:
relative to the frequency source X
0
〇
P0-06
Frequency offset of
auxiliary frequency
source for Y operation
0%
~
150%
100%
〇
P0-07
Frequency source
overlay selection
Unit position: frequency source selection
0: main frequency source X
1: primary and secondary operations (the
operation relationship is determined by ten
bits)
2: Main frequency source X and auxiliary
frequency source Y are switched
3: Main frequency source X and main and
auxiliary operation result switching
4: Auxiliary frequency source Y and main
and auxiliary operation result switching
Ten digits: frequency source primary and
secondary operation relationship
0: main + auxiliary 1: main - auxiliary
2: the maximum of the two 3: the minimum
of the two
00
〇
P0-08
Preset frequency
0.00Hz
~
Maximum frequency
(
P0-10
)
50.00Hz
〇