74
Chapter 6 P4 input terminal
K1
K2 Run
1
0
Forward
0
1
Reverse
1
1 stop
0
0
stop
values.
Schedule 2 Acceleration/deceleration time selection terminal function description
Terminal
2
Terminal
1
Acceleration or
deceleration time
selection
Corresponding parameter
OFF
OFF Acceleration time 1
P0-17
、
P0-18
OFF
ON
Acceleration time 2
P8-03
、
P8-04
ON
OFF Acceleration time 3
P8-05
、
P8-06
ON
ON
Acceleration time 4
P8-07
、
P8-08
P4-10
Input terminal filter time
0.000s
~
1.000s
Default
:
0.010s
Set the software filter time for the terminal status. If the input terminal is susceptible to
interference and cause malfunction, increase this parameter to enhance the anti-interference
ability. However, this parameter increase will cause the X terminal to respond slowly.
P4-11
Terminal command mode
0: two-wire type 1: two-wire type 2
2: Three-wire type 1 3: Three-wire
type 2
Default
:
0
This parameter defines four different ways to control the operation of the drive via
external terminals.
0: Two-wire mode 1: The positive and negative running of the motor is determined by
terminals X1 and X2.
Terminal function settings are as follows:
Terminal
Function code Setting value
Description
Terminal
command mode
P4-11
0
Two-line type 1
X1
P4-00
1
Forward running (X1)
X2
P4-01
2
Reverse run (X2)
T
able 6-6 Two-wire mode 1
1: Two-wire mode 2, in this mode, the X1 terminal function is the operation
enable terminal, and the X2 terminal function determines the running direction. The
terminal function settings are as follows:
Terminal
Function code Setting value description
K2
X1 Forward
(
FWD
)
X2 Reverse
(
REV
)
COM
K1