Chapter 5 Function parameter
37
PA-25
PID integral attribute
Unit’s
:
Integral separation
0
:
Invalid
1
:
Valid
Ten’s
:
Whether to stop integration after
output to the limit
0: Continue to integrate 1: Stop the
points
00
〇
PA-26
PID feedback loss
detection value
0.0%
:
no judge feedback loss 0.1%
~
100.0
%
0.0%
〇
PA-27
PID feedback loss
detection time
0.0s
~
20.0s
0.0s
〇
PA-28
PID shutdown
operation
0: stop does not operate 1: stop operation
0
〇
Pb Group Swing frequency, fixed length and counting
function
code
Parameter Name
Setting Range
Default Prop
erty
Pb-00
Swing frequency
setting method
0
:
Relative to the center frequency 1
:
Relative to the Maximum frequency
0
〇
Pb-01
Swing frequency range
0.0%
~
100.0%
0.0%
〇
Pb-02
Kick frequency
amplitude
0.0%
~
50.0%
0.0%
〇
Pb-03
Wobble cycle
0.1s
~
3000.0s
10.0s
〇
Pb-04
Swing frequency
triangle wave rise time
0.1%
~
100.0%
50.0%
〇
Pb-05
Set length
0m
~
65535m
1000m
〇
Pb-06
Actual length
0m
~
65535m
0m
〇
Pb-07
Pulse number per
meter
0.1
~
6553.5
100.0
〇
Pb-08
Set count value
1
~
65535
1000
〇
Pb-09
Specified count value
1
~
65535
1000
〇
PC Group Multi-segment instruction, simple PLC
function
code
Parameter Name
Setting Range
Default Prop
erty
PC-00
Multi-segment
instruction 0
-100.0%
~
100.0%
0.0%
〇
PC-01
Multi-segment
instruction 1
-100.0%
~
100.0%
0.0%
〇
PC-02
Multi-segment
instruction 2
-100.0%
~
100.0%
0.0%
〇
PC-03
Multi-segment
instruction 3
-100.0%
~
100.0%
0.0%
〇